Plan Review Notes For Permit 18060258
Permit Number 18060258
Review Stop E
Sequence Number 3
Notes
Date Text
2019-01-11 17:59:13FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PERMIT NEEDS TO BE ISSUED TO A LOW VOLTAGE OR
 ELECTRICAL CONTRACTOR (EC) GENERAL CONTRACTOR IS NOT
 ALLOWED TO PULL PERMIT FOR THIS TYPE OF WORK. NOT
 COMPLETED NEED TO CHANGE PERMIT TO BUILDING PERMIT WITH
 SUBS
  
 NEED CUT SHEETS FOR ALL CAMERAS, MOTION SENSORS, KEY
 PADS, CARD READERS, CABLES, ECT, ECT NOT DONE
  
 ALL EQUIPMENT SHALL BE LISTED AND USED INACCORDANCE
 WITH THE MANUFACTURERS INSTALLATION INSTRUCTIONS
 COMPLETED
  
 SHEET T2.10 NOT SURE WHAT PLAN IS SHOWING? COMPLETED
  
 SHEET T3.01 SEVERAL SYMBOLS NOT SHOWN IN LEGEND PP, NS,
 AMAG, PACS, PLC COMPLETED
  
 VALUE OF THE WORK SEEMS LOW PLEASE SUBMIT A SIGNED
 CONTRACT FOR THE WORK. NOT COMPLETED
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE
 LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL