Date |
Text |
2018-07-06 11:31:30 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| NFPA 70 2014 EDITION |
| |
| JAKE LEAHY |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6713 |
| [email protected] |
| |
| |
| PLANS INDICATE LOW VOLTAGE AND HIGH VOLTAGE TWO |
| SEPARATE PERMIT WILL BE REQUIRED |
| |
| FIRE ALARM AND ACCESS CONTROL SHOULD BE DONE ON |
| SEPARATE PLANS AND SEPARATE PERMITS. |
| |
| NEED CUT SHEETS FOR ALL CAMERAS, MOTION SENSORS, KEY |
| PADS, CARD READERS, CABLES, ECT, ECT |
| |
| PANEL SCHEDULES NEED TO IDENTIFY CIRCUITS NOT JUST AS |
| EXISTING. |
| |
| ALL EQUIPMENT SHALL BE LISTED AND USED IN ACCORDANCE |
| WITH THE MANUFACTURERS INSTALLATION INSTRUCTIONS. |
| |
| 110.3 EXAMINATION, IDENTIFICATION, INSTALLATION, AND |
| USE OF EQUIPMENT |
| ( B) INSTALLATION AND USE. LISTED OR LABELED EQUIPMENT |
| SHALL BE INSTALLED AND USED IN ACCORDANCE WITH ANY |
| INSTRUCTIONS INCLUDED |
| IN THE LISTING OR LABELING. |
| |
| CHANGING OUT COMPONENTS OF DIFFERENT SYSTEMS SHALL BE |
| LISTED IN ACCORDANCE WITH THE MANUFACTURERS |
| SPECIFICATIONS. |
| |
| VALUE OF THE WORK SEEMS LOW THERE IS A SIGNIFICANT |
| AMOUNT OF WORK SHOWN ON THESE PLANS. |
| |
| FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS |
| SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING |
| ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE |
| LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION |
| COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), |
| AS PUBLISHED BY INTERNATIONAL CODE CONGRESS. |
| FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE |
| BUILDING OFFICIAL |