2018-08-01 06:23:091) THE POOL PLANS SHOW TDH CALCULATIONS BASED ON THE
 SIMPLIFIED TDH CALCULATION METHOD. THIS METHOD IS
 ALLOWED IN THE 2006 VERSION OF APSP 7 BUT IS NO LONGER
 ALLOWED IN THE 2013 EDITION OF APSP 7 WHICH HAS BEEN
 ADOPTED BY THE 2017.
 FBC. TOTAL DYNAMIC HEAD CALCULATIONS SHALL BE DONE IN
 ACCORDANCE WITH 2013 APSP 7 SEC.4.4.9.1.
 2) TWO PUMP CURVES HAVE BEEN PROVIDED BUT THERE IS NO
 INDICATION ON EITHER CURVE WHICH CURVE KEY IS SPECIFIC
 TO THE TDH CALCULATIONS. THERE ARE DIFFERENT RPM'S ON
 THE CURVES. CLARRIFY WHICH ONE.
  