Plan Review Notes
Plan Review Notes For Permit 18060232
Permit Number 18060232
Review Stop P
Sequence Number 2
Notes
Date Text
2018-07-16 08:08:491) SHT. 2 OF 4 - APSP/ANSI-7 BOX - THE PLAN STILL
 STATES THAT THE MAXIMUM FLOW RATE OF THE SYSTEM IS
 BASED ON THE MAXIMUM FLOW FROM THE PUMP CURVE. REMOVE
 THIS NOTE FROM BOTH SETS OF PLANS.
 2) TOTAL DYNAMIC HEAD CALCULATIONS HAVE NOT BEEN
 SUBMITTED AS PREVIOUSLY REQUESTED. THERE IS A CLOUDED
 AREA WITH TDH NUMBERS FOR THE PIPE, FITTINGS AND
 FILTER. THESE ARE NOT CALCULATIONS. 2ND REQUEST.
 3) . IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS
 SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL. THIS
 IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE
 TDH CALCULATIONS. 2ND REQUEST.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  