2018-06-15 05:50:30 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PERMIT APPLICATION SAYS KEISER UNIVERSITY BUT |
| ADDRESS SAYS 1601 FORUM PLACE, PICTURES PROVIDED OF |
| SITE ARE OF1601 FORUM PLACE. PLANS SAY 2600 MILITARY |
| TRAIL. |
| IF THIS APPLICATION IS FOR THE NEW ATHLETIC FACILITY |
| BEING BUILT THE PERMITTED ADDRESS IS 2331 NORTHWOOD |
| UNIVERSITY. CORRECT ADDRESS ISSUE. |
| |
| 2. A PHYSICAL COPY OF AN ELECTRONICALLY OR DIGITALLY |
| SIGNED, DATED AND SEALED DOCUMENT IS NOT A VALID |
| SIGNED, DATED AND SEALED DOCUMENT. SIMILARLY, AN |
| ELECTRONIC DOCUMENT (PDF, SCAN OR FAX COPY) OF A |
| PHYSICALLY SIGNED, DATED AND SEALED DOCUMENT IS NOT A |
| VALID SIGNED, DATED AND SEALED DOCUMENT. |
| F.S. 471/F.A.C. 61G15-23.004 (3)(C)(3) |
| |
| 3. VALUE TOO LOW, PROVIDE COPY OF SIGNED CONTRACT WITH |
| SCOPE AND VALUE OF WORK, TO INCLUDE ALL MATERIALS AND |
| LABOR. FBC 109.3 |
| |
| 4. DISCONNECT FOR 120V BEFORE IT ENTERS SIGN REQUIRED |
| WITHIN SIGHT OF SIGN. NEC. 600.6A(1) |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |