2018-06-24 08:46:17ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PERMIT APPLICATION AND PICTURES OF PROPERTY ARE FOR
 1601 FORUM PLACE BUT ELECTRICAL DRAWING IS FOR KEISER
 UNIVERSITY 2600 NORTH MILITARY TRAIL. PLEASE CORRECT
 ADDRESS ISSUES.
  
 2. ELECTRICAL NOTE #11 DOES NOT MEET DISCONNECT
 REQUIREMENTS OF 600.6A(1) NEC.
  
 END OF COMMENTS.
  