Plan Review Notes For Permit 18060140 |
Permit Number |
18060140 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-06-26 17:59:53 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE CONCRETE PAD SCHEDULE FOR THE AMERICAST | | GENERATOR PAD REQUIRES A MINIMUM UNIT WEIGHT OF 526 | | LBS. FOR THE 22KW GENERATOR UNIT. THE SPECIFICATIONS | | FOR THE 22KW GENERATOR THAT WAS SUBMITTED SPECIFIES THE | | UNIT WEIGHT AS 466 LBS. WHICH DOES NOT MEET THE | | REQUIRED MINIMUM. FBC 107.2.1 | | |
|