Plan Review Notes
Plan Review Notes For Permit 18060140
Permit Number 18060140
Review Stop B
Sequence Number 1
Notes
Date Text
2018-06-26 17:59:53PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE CONCRETE PAD SCHEDULE FOR THE AMERICAST
 GENERATOR PAD REQUIRES A MINIMUM UNIT WEIGHT OF 526
 LBS. FOR THE 22KW GENERATOR UNIT. THE SPECIFICATIONS
 FOR THE 22KW GENERATOR THAT WAS SUBMITTED SPECIFIES THE
 UNIT WEIGHT AS 466 LBS. WHICH DOES NOT MEET THE
 REQUIRED MINIMUM. FBC 107.2.1
  