2018-06-22 14:01:41 | 1) THE SHUTOFF VALVE FOR THE INTERIOR PIPING SHALL BE | | LOCATED UPSTREAM OF THE PRESSURE REGULATOR PER 2017 | | FBC-FUEL GAS SEC.409.4. | | 2) THE PIPE AT THE TEE FOR THE POOL HEATER IS SHOWN AS | | RIDGID GALVANIZED AND ALSO AS PE. CLARIFY. | | 3) INDICATE ON THE GAS PLANS WHICH SIZING TABLE IS | | BEING USED FOR THE LOW PRESSURE SCH. 40 METALLIC PIPE. | | 4) GAS PLANS ON FILE WITH THE CITY SHOW AN 1 1/4 INCH | | GALVANIZED LINE AT THE GAS METER OUTLET AND THE | | SUBMITTED PLANS SHOW AN EXISTING 3/4 INCH LINE. | | CLARIFY. | | 5) PLANS ON FILE WITH THE CITY SHOW A BTU LOAD OF | | 378,000 AND THE SUBMITTED PLANS SHOW AN EXISTING BTU | | LOAD OF 525,000. CLARIFY. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|