Plan Review Notes
Plan Review Notes For Permit 18060138
Permit Number 18060138
Review Stop G
Sequence Number 1
Notes
Date Text
2018-06-22 14:01:411) THE SHUTOFF VALVE FOR THE INTERIOR PIPING SHALL BE
 LOCATED UPSTREAM OF THE PRESSURE REGULATOR PER 2017
 FBC-FUEL GAS SEC.409.4.
 2) THE PIPE AT THE TEE FOR THE POOL HEATER IS SHOWN AS
 RIDGID GALVANIZED AND ALSO AS PE. CLARIFY.
 3) INDICATE ON THE GAS PLANS WHICH SIZING TABLE IS
 BEING USED FOR THE LOW PRESSURE SCH. 40 METALLIC PIPE.
 4) GAS PLANS ON FILE WITH THE CITY SHOW AN 1 1/4 INCH
 GALVANIZED LINE AT THE GAS METER OUTLET AND THE
 SUBMITTED PLANS SHOW AN EXISTING 3/4 INCH LINE.
 CLARIFY.
 5) PLANS ON FILE WITH THE CITY SHOW A BTU LOAD OF
 378,000 AND THE SUBMITTED PLANS SHOW AN EXISTING BTU
 LOAD OF 525,000. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  