Plan Review Notes For Permit 18060126 |
Permit Number |
18060126 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-08-11 16:42:52 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. SEE PREVIOUS LIST, ITEM #1 (SUBSTANTIAL IMPROVEMENT | | DETERMINATION). | | | | A DOCUMENT ENTITLED "INSURABLE VALUE: REPLACEMENT COST | | SUMMARY" WAS PROVIDED. SEE FEMA 758, 4.5.3, ACTUAL CASH | | VALUE (METHOD OF DETERMINING VALUE). IF YOU WISH TO USE | | THIS METHOD, PLEAE REVISE TO PROVIDE DATA CONSISTENT | | WITH FEMA'S GUIDELINES. ALSO PROVIDE INFORMATION ABOUT | | THE PREPARER. | | | | 2.FBC B TABLE 1604.5, RISK CATEGORY III IS REQUIRED FOR | | ASSEMBLY OCCUPANCY WITH AN OCCUPANT LOAD GREATER THAN | | 300, SHEET S2. SEE ALSO FBC EB 807. | | | | 2ND REVIEW, THIS WAS REVISED, BUT BASED ON THE WIND | | MAPS (AND THE ATC WINDSPEED SITE) IT APPEARS THAT RISK | | CATEGORY III IS IN THE 180MPH WIND ZONE. | | | | 3. OK | | | | 4. COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT | | OF UNDERSTANDING; THIS HAS BEEN SENT VIA EMAIL TO | | CONTRACTOR. | | | | 5. PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL | | PROPOSED INSPECTORS. | | | | 6. OK | | | | | | |
|