Plan Review Notes
Plan Review Notes For Permit 18060126
Permit Number 18060126
Review Stop B
Sequence Number 2
Notes
Date Text
2018-08-11 16:42:52****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SEE PREVIOUS LIST, ITEM #1 (SUBSTANTIAL IMPROVEMENT
 DETERMINATION).
  
 A DOCUMENT ENTITLED "INSURABLE VALUE: REPLACEMENT COST
 SUMMARY" WAS PROVIDED. SEE FEMA 758, 4.5.3, ACTUAL CASH
 VALUE (METHOD OF DETERMINING VALUE). IF YOU WISH TO USE
 THIS METHOD, PLEAE REVISE TO PROVIDE DATA CONSISTENT
 WITH FEMA'S GUIDELINES. ALSO PROVIDE INFORMATION ABOUT
 THE PREPARER.
  
 2.FBC B TABLE 1604.5, RISK CATEGORY III IS REQUIRED FOR
 ASSEMBLY OCCUPANCY WITH AN OCCUPANT LOAD GREATER THAN
 300, SHEET S2. SEE ALSO FBC EB 807.
  
 2ND REVIEW, THIS WAS REVISED, BUT BASED ON THE WIND
 MAPS (AND THE ATC WINDSPEED SITE) IT APPEARS THAT RISK
 CATEGORY III IS IN THE 180MPH WIND ZONE.
  
 3. OK
  
 4. COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT
 OF UNDERSTANDING; THIS HAS BEEN SENT VIA EMAIL TO
 CONTRACTOR.
  
 5. PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL
 PROPOSED INSPECTORS.
  
 6. OK
  
  
  