2018-06-29 12:19:00 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. ALL MAINS SHOULD BE GROUPED PER NEC 230.72. RISER |
| SHOWS AN 800 AMP SERVICE IN ONE LOCATION, A 600 AMP |
| SERVICE IN ANOTHER LOCATION, AND THEN THE ADDITION OF |
| THE 1200 AMP SERVICE IN A THIRD LOCATION. THIS WILL NOT |
| BE ACCEPTABLE PER CODE. PREVIOUS APPROVAL OF PLAN FOR |
| 1200 AMP SERVICE WILL NOT BE PERMITTED IN THIS |
| LOCATION. PROVIDE CORRECTION SO THAT MAINS ARE GROUPED. |
| NEC 230.72, 230.2 |
| 2. PROVIDE JUSTIFICATION FOR ADDITIONAL 1200 AMP |
| SERVICE. THE LOAD SHOWN ON THIS PANEL IS APPROXIMATELY |
| 112 AMPS, ALTHOUGH THAT IS INCORRECT BECAUSE NO VALUE |
| HAS BEEN ADDED FOR PANEL LPA. SEE COMMENT 3 FOR LOAD |
| CALCULATION INFORMATION. NEC 230.2 |
| 3. PROVIDE LOAD CALCULATION FOR EACH SERVICE INCLUDING |
| EXISTING AND PROPOSED LOADS TO SHOW WHETHER THE |
| EXISTING SERVICE IS ADEQUATE OR NOT FOR THE ADDITIONAL |
| LOAD. ADDITIONALLY, THE LOAD CALCULATION SHOULD BE |
| COMPLETED FOR ALL THREE PHASES. CURRENTLY, ONLY TWO OF |
| THE PHASES ARE SHOWN. NEC 220; WPB FBC 107.2.1 |
| 4. RISER DIAGRAM SHOWS A NEW PANEL LP FEED FROM |
| EXISTING 600 AMP SERVICE. WHERE IS THIS PANEL LOCATED? |
| THERE IS NO PANEL SCHEDULE FOR THIS? PROVIDE DETAILS. |
| WPB FBC 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |