2018-06-16 19:34:07 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. THIS STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD |
| AREA. IT IS NOT CLEAR IF THIS IS A "SUBSTANTIAL |
| IMPROVEMENT"; CUMULATIVE 5 YEAR IMPROVEMENTS EXCEED |
| OVER 50% OF STRUCTURE VALUE. PROVIDE INFORMATION |
| REGARDING THE PAST FIVE YEARS OF IMPROVEMENTS ON THIS |
| STRUCTURE, VALUE OF THIS STRUCTURE, FBC B 1622. PLEASE |
| FEEL FREE TO CONTACT ME IF YOU NEED ASSISTANCE. |
| ALTERNATIVELY, YOU COULD SHOW COMPLIANCE WITH THE |
| REQUIREMENTS FOR NEW STRUCTURES - FINISHED FLOOR AND |
| ALL EQUIPMENT SERVICING THE BUILDING TO BE AT OR ABOVE |
| 14.2 NAVD88, OR PROVIDE DRY FLOODPROOFING TO 14.2 |
| NAVD88, EXTERIOR EQUIPMENT ELEVATED TO MINIMUM 14.2 |
| NAVD88. |
| |
| 2.FBC B TABLE 1604.5, RISK CATEGORY III IS REQUIRED FOR |
| ASSEMBLY OCCUPANCY WITH AN OCCUPANT LOAD GREATER THAN |
| 300, SHEET S2. SEE ALSO FBC EB 807. |
| |
| 3. 553.79(5), AS THIS IS AN ASSEMBLY OCCUPANCY WITH AN |
| OCCUPANT LOAD OVER 500, THIS IS CLASSIFIED AS A |
| THRESHOLD BUILDING. ALL PLANS PREPARED BY THE ARCHITECT |
| AND ENGINEER ARE TO INCLUDE THE THRESHOLD STATEMENT |
| REQUIRED BY FS553.79(7)(D). |
| |
| ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE |
| SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF |
| RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE |
| ARCHITECT?S OR ENGINEER?S KNOWLEDGE, THE PLANS AND |
| SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM |
| BUILDING CODES AND THE APPLICABLE FIRESAFETY STANDARDS |
| AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH |
| THIS CHAPTER 553 AND CHAPTER 633. |
| |
| 4. COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT |
| OF UNDERSTANDING; THIS HAS BEEN SENT VIA EMAIL TO |
| CONTRACTOR. |
| |
| 5. PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL |
| PROPOSED INSPECTORS. |
| |
| 6. THRESHOLD INSPECTION PLAN REQUIRED, FS553.79(5)A). |
| |
| |
| |