2018-06-27 08:01:371ST REVIEW: FBC 2017 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE A PIPING DIAGRAM THATS IS A MIN 1/8IN
 SCALE AND LEGIBLE THE ONE THAT WAS PROVIDED IS NOT. PER
 WPB AMEND TO FBC 107.2.1.3
 2. PROVIDE SIT PLAN THE SAT PHOTOGRAPH IS NOT CLEAR.
 PER WPB AMEND TO FBC 107.2.1.3, 107.2.5
 3. PLEASE INDICATE ON THE MANUFACTURE SPEC THE MODEL OF
 THE TANK AND TIE DOWN THAT YOU ARE USING THE PROPOSAL
 AND SPEC DON'T MATCH UP. PER PER WPB AMEND TO
 FBC107.2.1
 4. PROVIDE MSDS SHEETS FOR CHEMICAL STORED IN TANKS.
 PER WPB AMEND TO FBC107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  