Plan Review Notes
Plan Review Notes For Permit 18051514
Permit Number 18051514
Review Stop B
Sequence Number 1
Notes
Date Text
2018-06-06 17:48:13****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC R 905.2.2, REVISE APPLICATION TO INCLUDE ROOF
 SLOPE. THE INFORMATION PROVIDED ON THE APPLICATION -
 "SLOPE:552 FLAT:351" IS NOT CONSISTENT WITH THE
 BUILDING CODE. SLOPE TO BE SPECIFIED AS RISE AND RUN OR
 DEGREES.
  
 A DOUBLE UNDERLAYMENT IS REQUIRED FOR ROOF SLOPE LESS
 THAN 4/12. IF A DOUBLE UNDERLAYMENT IS REQUIRED, REVISE
 APPLICATION TO STATE THAT A DOUBLE LAYER WILL BE
 INSTALLED.
  
 2. IT APPEARS THAT THE LOW SLOPE ROOF IS IN THE SCOPE
 OF THIS PERMIT; PROVIDE PRODUCT APPROVAL WITH THE
 ASSEMBLY PROPOSED INDICATED. PROVIDE ENGINEERING IF
 REQUIRED.
  