2018-06-06 17:10:43ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) PURSUANT TO 94-305(B)(4) - MECHANICAL EQUIMENT MAY
 NOT PROJECT MORE THAN 4 FEET INTO A SETBACK. THEREFORE,
 THE GENERATOR SHOULD BE AT LEAST 6 FEET FROM THE
 PROPERTY LINE.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  