2018-06-22 19:06:061ST REVIEW: FBC FIFTH EDITION (2014) REFERENCE PRIMARY
 PERMIT 16040430
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF GENERATOR PAD PLANS. PROVIDE PAD
 DIMENSIONS AND LOCATION. SPECIFY THE SIZE, TYPE AND
 QUANITY OF ANCHORS FOR THE GENERATOR TO SLAB
 CONNECTIONS. FBC 107.2.1
  
 2) THE PROJECT IS LOCATED IN AN A5 SPECIAL FLOOD HAZARD
 ZONE AN ELEVATION CERTIFICATE WILL BE REQUIRED TO BE
 SUBMITTED AND APPROVED BEFORE FINAL INSPECTION. THE
 MINIMUM ELEVATION FOR THIS PROJECT IS 7.5' NGVD BASED
 ON THE FIRMS IN EFFECT AT THE TIME THE SINGLE FAMILY
 HOME THIS GENERATOR WILL SERVICE WAS PERMITTED.
  