Plan Review Notes For Permit 18051467 |
Permit Number |
18051467 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-06-22 19:06:06 | 1ST REVIEW: FBC FIFTH EDITION (2014) REFERENCE PRIMARY | | PERMIT 16040430 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT TWO SETS OF GENERATOR PAD PLANS. PROVIDE PAD | | DIMENSIONS AND LOCATION. SPECIFY THE SIZE, TYPE AND | | QUANITY OF ANCHORS FOR THE GENERATOR TO SLAB | | CONNECTIONS. FBC 107.2.1 | | | | 2) THE PROJECT IS LOCATED IN AN A5 SPECIAL FLOOD HAZARD | | ZONE AN ELEVATION CERTIFICATE WILL BE REQUIRED TO BE | | SUBMITTED AND APPROVED BEFORE FINAL INSPECTION. THE | | MINIMUM ELEVATION FOR THIS PROJECT IS 7.5' NGVD BASED | | ON THE FIRMS IN EFFECT AT THE TIME THE SINGLE FAMILY | | HOME THIS GENERATOR WILL SERVICE WAS PERMITTED. | | |
|