Date |
Text |
2018-06-28 13:28:53 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) SHEET A020 - THERE ARE A PAIR OF DOUBLE DOORS |
| LEADING OUT OF THE BALL ROOM, 151A & 151B. THIS IS A |
| MIXED NON-SEPARATED OCCUPANY. THE BALL ROOM IS AN |
| ASSEMBLY SPACE. |
| |
| PER NFPA 101, CHAPTER 12, NEW ASSEMBLY, |
| |
| 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM |
| AN AREA HAVING |
| AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE |
| PERMITTED TO BE |
| PROVIDED WITH A LATCH OR LOCK ONLY IF THE LATCH OR LOCK |
| IS PANIC |
| HARDWARE OR FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7, |
| UNLESS |
| OTHERWISE PERMITTED BY ONE OF THE FOLLOWING: |
| |
| THERE IS NO INDICATION OF PANIC HARDWARE FOR THESE |
| DOOR. |
| |
| THERE IS AN INDICATION OF HARDWARE SET 4, PUT THE |
| HARDWARE DETAILS COULD NOT BE READILY INDETIFIED IN THE |
| PLAN SHEETS. |
| |
| PLEASE PROVIDE DETAILS FOR THESE DOORS THAT MEET THE |
| REQUIRMENTS OF THE CODE. |
| |
| |
| |
| 2) ELECTRICAL SHHETS - THERE ARE INDICATIONS OF FIRE |
| ALARM EQUIPMENT; HOWEVER, NO INDICATIONS OF FIRE ALARM |
| WORK OR SHOP DRAWINGS. |
| |
| ALL WORK ON ANY FIRE ALARM EQUIPMENT OF SYSTEM SHALL BE |
| DONE UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE |
| SAFETY CONTRACTORS. |
| |
| PLEASE PROVIE AN APPLICABLE NOTE. |
| |
| |
| |
| 3) SHEET A002 - THERE ARE CHAIRS INDICATED IN THE BALL |
| ROOM. ARE THESE CHAIRS PERMANENT. TEMPORARY, LOOSE OR |
| INTERLOCKING? |
| |
| PLEASE PROVIDE CHAIR DETAILS. |
| |
| |
| |
| |
| 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |
| |
| |