Plan Review Notes
Plan Review Notes For Permit 18051461
Permit Number 18051461
Review Stop E
Sequence Number 1
Notes
Date Text
2018-08-06 16:14:54CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHEET E001, APPLICABLE CODES, NOTE 1 (N), SHOWS THE
 2014 FBC AS BASIS FOR DESIGN. THIS IS NOT THE CURRENT
 CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE CODES
 ABOVE.)
 2. SHEET E001, NOTE 54, SHOWS THE 2014 FBC ENERGY
 CONSERVATION AS BASIS FOR DESIGN. THIS IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE
 CODES ABOVE.)
 3. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 4. PROVIDE LOAD CALCULATION FOR PANEL HB, PANEL DPB,
 AND PANEL BB, INCLUDE EXISTING AND NEW LOADS TO CONFIRM
 CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  