2018-08-06 16:14:54 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. SHEET E001, APPLICABLE CODES, NOTE 1 (N), SHOWS THE |
| 2014 FBC AS BASIS FOR DESIGN. THIS IS NOT THE CURRENT |
| CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE CODES |
| ABOVE.) |
| 2. SHEET E001, NOTE 54, SHOWS THE 2014 FBC ENERGY |
| CONSERVATION AS BASIS FOR DESIGN. THIS IS NOT THE |
| CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE |
| CODES ABOVE.) |
| 3. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES |
| EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN |
| RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2 |
| 4. PROVIDE LOAD CALCULATION FOR PANEL HB, PANEL DPB, |
| AND PANEL BB, INCLUDE EXISTING AND NEW LOADS TO CONFIRM |
| CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD |
| SHEETS?. |
| |