2018-09-11 08:38:50PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD ENGINEERING DOCUMENTS DO NOT HAVE
 THE ORIGINAL HANDWRITTEN SIGNATURE OF THE ENGINEER ON
 THE SEAL. FAC 61G15-23.003 PROCEDURES FOR PHYSICALLY
 SIGNING AND SEALING PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS. ENGINEERING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS WHICH MUST BE SIGNED, DATED
 AND SEALED IN ACCORDANCE WITH THE PROVISIONS OF SECTION
 471.025, F.S., AND RULE 61G15-23.001, F.A.C. MAY BE
 PHYSICALLY SIGNED, DATED AND SEALED AS PROVIDED HEREIN
 BY THE PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE'S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  
 2) THE WIDTH DIMENSION FOR THE 20KW GENERATOR LISTED IN
 THE MANUFACTURER'S SPECIFICATIONS EXCEEDS THE MAXIMUM
 UNIT DIMENSION THAT IS ALLOWED BY THE PAD ENGINEERING.
 FBC 107.2.1
  
 3) THE MINIMUM WEIGHT FOR THE UNIT THAT IS REQUIRED BY
 THE PAD ENGINEERING IS 535 LBS. AND THE WEIGHT FOR THIS
 UNIT IS 500 LBS. PER THE MANUFACTURER'S SPECIFICATIONS.
 FBC 107.2.1
  