2018-06-21 09:47:46 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC SIXTH EDITION (2017) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE GENERATOR PAD ENGINEERING DOCUMENTS DO NOT HAVE |
| THE ORIGINAL HANDWRITTEN SIGNATURE OF THE ENGINEER ON |
| THE SEAL. FAC 61G15-23.003 PROCEDURES FOR PHYSICALLY |
| SIGNING AND SEALING PLANS, SPECIFICATIONS, REPORTS OR |
| OTHER DOCUMENTS. |
| ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN |
| ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025, |
| F.S., AND RULE 61G15-23.001, F.A.C. MAY BE PHYSICALLY |
| SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE |
| PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. |
| (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE |
| LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE |
| SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR |
| COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE |
| USED. |
| (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY |
| CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY |
| OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE |
| REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL |
| NOT RENDER THE SIGNATURE ILLEGIBLE. |
| |
| 2) THE PAD DOCUMENTS REFERENCE THE 2010 FLORIDA |
| BUILDING CODE AND THE CODE THAT APPLIES TO THIS PROJECT |
| IS THE 2017 FBC. FBC 102.2 |
| |
| 3) THE LENGTH DIMENSION FOR THE 20KW GENERATOR LISTED |
| IN THE MANUFACTURER'S SPECIFICATIONS EXCEEDS THE |
| MAXIMUM UNIT DIMENSION THAT IS ALLOWED BY THE PAD |
| ENGINEERING. FBC 107.2.1 |
| |