2018-06-03 07:22:111) THE SUCTION OUTLET SAGETY CCOMPLIANCE DATA SHEET
 SHOWS THAT THE SYSTEM FLOW RATE HAS BEEN DETERMINED BY
 THE MAXIMUM FLOW FROM THE PUMP CURVE. THIS METHOD IS NO
 LONGER PERMITTED BY APSP/ANSI-7 2013 EDITION SEC.
 4.4.9. TOTAL DYNAMIC HEAD CALCULATIONS ARE REQUIRED.
 2) IDENTIFY ON THE PUMP CURVE GRAPH THE PUMP BEING
 INSTALLED. SUBMIT A CURVE SHOWING THE GRADIENT LINES SO
 THE MAXIMUM FLOW CAN BE DETERMINED FROM THE TDH
 CALCULATIONS.
 3) SHT. 2 OF 3 REFERS TO SEC. 424 OF THE FLORIDA
 BULDING CODE. THIS CODE SECTION IS FOR CHILDREN'S PLAY
 STRUCTURES, NOT SWIMMING POOLS. PLEASE REVISE THE NOTE
 TO THE CORRECT CODE SECTION(S).
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW