Plan Review Notes For Permit 18051366 |
Permit Number |
18051366 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-06-03 07:22:11 | 1) THE SUCTION OUTLET SAGETY CCOMPLIANCE DATA SHEET | | SHOWS THAT THE SYSTEM FLOW RATE HAS BEEN DETERMINED BY | | THE MAXIMUM FLOW FROM THE PUMP CURVE. THIS METHOD IS NO | | LONGER PERMITTED BY APSP/ANSI-7 2013 EDITION SEC. | | 4.4.9. TOTAL DYNAMIC HEAD CALCULATIONS ARE REQUIRED. | | 2) IDENTIFY ON THE PUMP CURVE GRAPH THE PUMP BEING | | INSTALLED. SUBMIT A CURVE SHOWING THE GRADIENT LINES SO | | THE MAXIMUM FLOW CAN BE DETERMINED FROM THE TDH | | CALCULATIONS. | | 3) SHT. 2 OF 3 REFERS TO SEC. 424 OF THE FLORIDA | | BULDING CODE. THIS CODE SECTION IS FOR CHILDREN'S PLAY | | STRUCTURES, NOT SWIMMING POOLS. PLEASE REVISE THE NOTE | | TO THE CORRECT CODE SECTION(S). | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | |
|