2018-06-01 07:22:30 | 06/01/2018 1ST REVIEW GAS AND PLUMBING**DENIED** |
| |
| 1) SUPPLY CURRENT INSTALATION MAUNAL. THE ONE YOU HAVE |
| PROVIDE IS FOR THE REU-VB2735WD-US AND THE MODEL |
| INSTALLED ON-SITE IS REU-VC2837WD-US. SUBMIT |
| MANUFACTURER?S SPECIFICATION SHEETS / INSTALLATION |
| MANUAL FOR ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND FBC-2017 FUEL GAS CODE |
| SEC. 402.2, AND 301.3 OR 2017 FBC-RES. SEC. G2404.3. |
| GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT |
| SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC |
| SEC.305.1, FBC-RES. SEC.G2408.1. |
| |
| 2) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS |
| THE ONLY GAS APPLIANCE ON THIS SYSTEM? IF NOT, SUBMIT A |
| COMPLETE GAS RISER SHOWING ALL PIPE SIZES, TYPE OF |
| PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS OUTLET, |
| THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE SYSTEM, |
| THE TYPE OF GAS AND THE TOTAL BTU LOAD ON THE SYSTEM. |
| THESE REQUIREMENTS ALSO APPLY TO A NEW GAS SYSTEM. |
| |
| 3) SUBMIT TWO COPIES OF A BUILDING PLAN SHOWING THE |
| LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. |
| |
| 4) ) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| DESIGN OF THIS GAS SYSTEM.USE OF THE SIZING TABLE FROM |
| A EXPIRED MANUFACTURES MANUAL DOES NOT COMPLY. REFER TO |
| THE 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND |
| TABLES 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC. |
| G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3. |
| |
| 5) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| LENGTH OF ALL CUT SECTIONS OF PIPE AS THIS INSTALL WAS |
| DONE WITHOUT A PERMIT AND THE DRIP LEG HAS BEEN |
| REMOVED. PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. |
| OR 2017 FBC-RES SEC. G2413.4.1, G2413.4.2. |
| |
| 6) VALUE OF JOB IS TOO LOW AND MUST INCLUDE THE COST OF |
| THE TANKLESS ITSELF EVEN IF OWNER SUPPLIES AS IN THIS |
| CASE. PROVIDE A SIGNED BONA FIDE CONTRACT PER WPB AMEND |
| TO THE FBC 109.3. |
| |
| TIM HUNT |
| PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |
| CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| 561-805-6695 |
| [email protected] |