Plan Review Notes For Permit 18051345 |
Permit Number |
18051345 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-06-04 12:51:11 | PERMIT # 18051345 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | PROVIDE AN EXTERIOR KNOXBOX KEY SAFE, SWITCH OR PADLOCK | | TO ALLOW EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO | | THE BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE, | | SWITCH, OR PADLOCK CAN BE ORDERED FROM WWW.KNOXBOX.COM. | | | | PER SECTION 18.2.3.4.1.1 (NFPA 1), FIRE DEPARTMENT | | ACCESS SHALL HAVE AN UNOBSTRUCTED WIDTH OF NOT LESS | | THAN 20 FEET AND AN UNOBSTRUCTED VERTICAL CLEARANCE OF | | NOT LESS THAN 13 FEET 6 INCHES. | | | | | | SUE ELLEN CALDERON | | ASSISTANT FIRE MARSHAL | | [email protected] | | |
|