Plan Review Notes
Plan Review Notes For Permit 18051320
Permit Number 18051320
Review Stop G
Sequence Number 2
Notes
Date Text
2018-07-30 07:26:081) EXISTING GAS PLANS IN CITY RECORDS SHOW THE LONGEST
 DISTANCE FROM THE METER TO THE MOST REMOTE OUTLET AS
 104 FEET. THIS DISTANCE SHALL BE USED IN THE SIZING OF
 THIS SYSTEM. 2017 FBCR- SEC. G2413.4.1.
 2) EXISTING GAS PLAN ON FILE WITH THE CITY SHOWS A 1
 INCH LINE TO THE INTERIOR EXISTING GAS FIXTURES BUT THE
 SUBMITTED GAS DRAWING SHOWS A 3/4 INCH LINE. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW