2018-06-03 06:54:391) EXISTING GAS PLPANS IN CITY RECORDS SHOW THE LONGEST
 DISTANCE FROM THE METER TO THE MOST REMOTE OUTLET AS
 104 FEET. THIS DISTANCE SHALL BE USED IN THE SIZING OF
 THIS SYSTEM. 2017 FBCR- SEC. G2413.4.1.
 2) THE PIPE SIZE OF THE SCH. 40 METALLIC PIPE AT THE
 OUTLET OF THE GAS METER SHALL BE 1 1/2 INCHES PER TABLE
 402.4 (2) OF 2017 FBC-FUEL GAS, 2017 FBCR TABLE G2413.4
 (2).
 3) THE GAS PLAN SHOWS A 3/4 INCH GALVANIZED LINE AT THE
 OUTLET OF THE GAS METER., PLEASE EXPLAIN HOW YOU WILL
 SUPPLY AN 1 1/4 INCH PE LINE WITH A 3/4 INCH GALVANIZED
 LINE.THE EXISTING PLAN ON RECORD SHOWS AN 1 1/2 INCH
 LINE.
 4) INDICATE ON THE PLAN HOW THE GALVANIZED PIPE WILL BE
 INSTALLED. WILL IT BE ATTACHED TO THE WALL OF THE
 STRUCTURE? SUBMIT ADDITIONAL INFO/DETAILS. WPB AMEND.
 TO FBC SEC. 107.2.1.
 5) SHOW THE DISTANCE FROM THE METER TO FURTHEST OUTLET
 TO THE APPLIANCES IN THE STRUCTURE.WPB AMEND. TO FBC
 SEC. 107.2.1.
 6) SHOW THE DISTANCE FROM THE EXISTING GAS METER TO THE
 POOL HEATER.WPB AMEND. TO FBC SEC. 107.2.1.
 7) SHOW THE POOL HEATER AS EXISTING O NTHE GAS PLAN.
  