Plan Review Notes For Permit 18051320 |
Permit Number |
18051320 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-06-03 06:54:39 | 1) EXISTING GAS PLPANS IN CITY RECORDS SHOW THE LONGEST | | DISTANCE FROM THE METER TO THE MOST REMOTE OUTLET AS | | 104 FEET. THIS DISTANCE SHALL BE USED IN THE SIZING OF | | THIS SYSTEM. 2017 FBCR- SEC. G2413.4.1. | | 2) THE PIPE SIZE OF THE SCH. 40 METALLIC PIPE AT THE | | OUTLET OF THE GAS METER SHALL BE 1 1/2 INCHES PER TABLE | | 402.4 (2) OF 2017 FBC-FUEL GAS, 2017 FBCR TABLE G2413.4 | | (2). | | 3) THE GAS PLAN SHOWS A 3/4 INCH GALVANIZED LINE AT THE | | OUTLET OF THE GAS METER., PLEASE EXPLAIN HOW YOU WILL | | SUPPLY AN 1 1/4 INCH PE LINE WITH A 3/4 INCH GALVANIZED | | LINE.THE EXISTING PLAN ON RECORD SHOWS AN 1 1/2 INCH | | LINE. | | 4) INDICATE ON THE PLAN HOW THE GALVANIZED PIPE WILL BE | | INSTALLED. WILL IT BE ATTACHED TO THE WALL OF THE | | STRUCTURE? SUBMIT ADDITIONAL INFO/DETAILS. WPB AMEND. | | TO FBC SEC. 107.2.1. | | 5) SHOW THE DISTANCE FROM THE METER TO FURTHEST OUTLET | | TO THE APPLIANCES IN THE STRUCTURE.WPB AMEND. TO FBC | | SEC. 107.2.1. | | 6) SHOW THE DISTANCE FROM THE EXISTING GAS METER TO THE | | POOL HEATER.WPB AMEND. TO FBC SEC. 107.2.1. | | 7) SHOW THE POOL HEATER AS EXISTING O NTHE GAS PLAN. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | |
|