2018-06-20 08:28:29 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE MODEL NUMBERS FOR THE GENERAC 22KW GENERATOR | | G007043-0 AND G007042-0 THAT'S SPECIFICATIONS WERE | | SUBMITTED ARE NOT LISTED IN THE GENERATOR TABLE ON THE | | AMERICAST PAD ENGINEERING. THEREFORE, THIS PAD CAN NOT | | BE USED WITH THIS GENERATOR. FBC-R 301.1 | | |
|