Plan Review Notes
Plan Review Notes For Permit 18051301
Permit Number 18051301
Review Stop P
Sequence Number 1
Notes
Date Text
2018-06-18 17:48:3206/18/18 1ST PLUMBING REVIEW**DENIED**
  
 1) PROVIDE THE MANUFACTURES COMPLETE MANUAL OF CHAIR
 FIXTURE EQUIPMENT SHOWING IT COMPLIES WITH ASSE 1070.
 FBC P 423.3
  
 2) EXISTING TANKLESS WATER HEATER IS A POINT OF USE
 ONLY IS WILL BE UNDERSIZED BY ADDING THIS NEW
 EQUIPMENT. HEATER MUST BE ABLE TO PRODUCE HOT WATER @
 FULL DEMAND. FBC P 604.3
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  