Plan Review Notes For Permit 18051301 |
Permit Number |
18051301 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-06-19 17:26:34 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #18051301 | | 6/19/18 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) REFER TO TABLE 403.3.1.1 FBC M FOR THE MINIMUM | | VENTILATION RATES FOR A NEW BARBER SHOP: A) AN EXHAUST | | SYSTEM WITH A MINIMUM AIRFLOW RATE 0.5 CFMS PER SQ. FT. | | B) OUTDOOR AIR FOR OCCUPANTS BASED ON 25 PERSONS PER | | 1000 SQ. FT. AT 7.5 CFMS PER PERSON + 0.6 CFMS PER SQ. | | FT. PLEASE PROVIDE MECHANICAL PLANS AND CALCULATIONS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|