Plan Review Notes
Plan Review Notes For Permit 18051301
Permit Number 18051301
Review Stop M
Sequence Number 1
Notes
Date Text
2018-06-19 17:26:341ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18051301
 6/19/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO TABLE 403.3.1.1 FBC M FOR THE MINIMUM
 VENTILATION RATES FOR A NEW BARBER SHOP: A) AN EXHAUST
 SYSTEM WITH A MINIMUM AIRFLOW RATE 0.5 CFMS PER SQ. FT.
 B) OUTDOOR AIR FOR OCCUPANTS BASED ON 25 PERSONS PER
 1000 SQ. FT. AT 7.5 CFMS PER PERSON + 0.6 CFMS PER SQ.
 FT. PLEASE PROVIDE MECHANICAL PLANS AND CALCULATIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  