Plan Review Notes
Plan Review Notes For Permit 18051291
Permit Number 18051291
Review Stop P
Sequence Number 1
Notes
Date Text
2018-06-14 09:07:501ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. P-2 IN THE MASTER BATHROOM THE VENT SHALL
 CONNECT BETWEEN THE TUB AND SHOWER TWO FIXTURES ARE NOT
 ALLOWED UPSTREAM OF THE VENT OR YOU CAN CONNECT THE
 FIXTURE BRANCH OF THE TUB TO THE BRANCH FOR THE
 LAVATORY'S. PER FBC PL 912.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  