Plan Review Notes
Plan Review Notes For Permit 18051269
Permit Number 18051269
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2018-08-15 11:21:401. SYSTEM DOES NOT APPEAR TO COMPLY WITH NFPA 101:9.6.4
 2. SEQUENCE OF OPERATION FOR SMOKE DETECTORS AT
 ELEVATOR LOBBY ARE REQUIRED.
 3. #17 - DUCT DETECTORS SHOULD BE SUPERVISORY; NOT
 GENERAL ALARM.
 4. NO APPARENT NOTIFICATION ON EXTERIOR OF THE BUILDING
 IF SYSTEM TO REMAIN AS "LOCAL ALARM ONLY".
  