Plan Review Notes For Permit 18051269 |
Permit Number |
18051269 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-08-15 11:21:40 | 1. SYSTEM DOES NOT APPEAR TO COMPLY WITH NFPA 101:9.6.4 | | 2. SEQUENCE OF OPERATION FOR SMOKE DETECTORS AT | | ELEVATOR LOBBY ARE REQUIRED. | | 3. #17 - DUCT DETECTORS SHOULD BE SUPERVISORY; NOT | | GENERAL ALARM. | | 4. NO APPARENT NOTIFICATION ON EXTERIOR OF THE BUILDING | | IF SYSTEM TO REMAIN AS "LOCAL ALARM ONLY". | | | | S. THOMAS | | 561-512-5336 |
|