Plan Review Notes
Plan Review Notes For Permit 18051263
Permit Number 18051263
Review Stop E
Sequence Number 3
Notes
Date Text
2018-10-07 09:02:40CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE COMPLETE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. THE LOAD CALCULATION POVIDED DOES
 NOT SHOW HOW THE DETERMINATION WAS MADE AND DISAGEES
 WITH THE LOAD LISTED AT PANEL SCHEDULE. NEC 215.2, 220,
 408.30; FBC RE E3602.2 (A LOAD CALCULATION SHOULD SHOW
 ALL LOADS AND THE CORRESPONDING VA FOR THAT LOAD. THIS
 SHOULD BE COMPLETED IN THE FORMAT PROVIDED IN THE FBC
 RESIDENTIAL. THE PARTIAL LOAD CALCULATION PROVIDED IS
 NOT ACCEPTABLE.)
 2. RISER DIAGRAM SHOWS THE METER FEEDING A MAIN BREAKER
 PANEL AHEAD OF THE DISCONNECT. PLAN SHOWS A METER AND
 DISCONNECT LOCATED OUTSIDE, AND A 150 AMP PANEL INSIDE.
 PROVIDE CLARIFICATION AND/OR CORRECTIONS. NEC 215.5,
 230, 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1 (WHAT IS SHOWN ON THE RISER
 DIAGRAM IS NOT THE SAME AS SHOWN ON PLAN. PROVIDE
 CORRECTION. RISER DIAGRAM SHOWS A FEED FROM THE METER
 TO THE INTERIOR PANEL WHICH IS LOCATED IN THE UTILITY.
 CONDUCTORS THAT ARE NOT PROTECTED BY A MAIN BREAKER OR
 DISCONNECT ARE NOT PERMITTED TO RUN THROUGH THE HOUSE
 IN THIS FASHION. PROVIDE EITHER A MAIN ON THE OUTSIDE
 OF THE HOME, OR INSTALL THE CONDUCTORS UNDER THE SLAB.
 PROVIDE CORRECTIONS. NEC 230.70, 250.6; FBC RE E3601.6
 3. OK
 4. OK
 5. OK
 6. OK
  
 NEW COMMENT:
  
 7. PLEASE BE ADVISED THAT THESE COMMENTS HAVE NOT BEEN
 ADDRESSED FOR THREE REVIEWS. IF UPON THE NEXT REVIEW,
 IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN AGAIN
 FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW IS
 REQUIRED. FLORIDA STATUTES STATE: WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. THE ADDITIONAL
 FEE FOR THIS PLAN WILL BE $950.00 . FS 553.80(2)(B)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  