2018-10-07 09:02:40 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| |
| 1. PROVIDE COMPLETE LOAD CALCULATION FOR SERVICE, |
| INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF |
| SERVICE IS ADEQUATE. THE LOAD CALCULATION POVIDED DOES |
| NOT SHOW HOW THE DETERMINATION WAS MADE AND DISAGEES |
| WITH THE LOAD LISTED AT PANEL SCHEDULE. NEC 215.2, 220, |
| 408.30; FBC RE E3602.2 (A LOAD CALCULATION SHOULD SHOW |
| ALL LOADS AND THE CORRESPONDING VA FOR THAT LOAD. THIS |
| SHOULD BE COMPLETED IN THE FORMAT PROVIDED IN THE FBC |
| RESIDENTIAL. THE PARTIAL LOAD CALCULATION PROVIDED IS |
| NOT ACCEPTABLE.) |
| 2. RISER DIAGRAM SHOWS THE METER FEEDING A MAIN BREAKER |
| PANEL AHEAD OF THE DISCONNECT. PLAN SHOWS A METER AND |
| DISCONNECT LOCATED OUTSIDE, AND A 150 AMP PANEL INSIDE. |
| PROVIDE CLARIFICATION AND/OR CORRECTIONS. NEC 215.5, |
| 230, 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, |
| E3609.3; WPB FBC 107.2.1 (WHAT IS SHOWN ON THE RISER |
| DIAGRAM IS NOT THE SAME AS SHOWN ON PLAN. PROVIDE |
| CORRECTION. RISER DIAGRAM SHOWS A FEED FROM THE METER |
| TO THE INTERIOR PANEL WHICH IS LOCATED IN THE UTILITY. |
| CONDUCTORS THAT ARE NOT PROTECTED BY A MAIN BREAKER OR |
| DISCONNECT ARE NOT PERMITTED TO RUN THROUGH THE HOUSE |
| IN THIS FASHION. PROVIDE EITHER A MAIN ON THE OUTSIDE |
| OF THE HOME, OR INSTALL THE CONDUCTORS UNDER THE SLAB. |
| PROVIDE CORRECTIONS. NEC 230.70, 250.6; FBC RE E3601.6 |
| 3. OK |
| 4. OK |
| 5. OK |
| 6. OK |
| |
| NEW COMMENT: |
| |
| 7. PLEASE BE ADVISED THAT THESE COMMENTS HAVE NOT BEEN |
| ADDRESSED FOR THREE REVIEWS. IF UPON THE NEXT REVIEW, |
| IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN AGAIN |
| FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW IS |
| REQUIRED. FLORIDA STATUTES STATE: WITH RESPECT TO |
| EVALUATION OF DESIGN PROFESSIONALS DOCUMENTS, IF A |
| LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO |
| ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND |
| ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY |
| THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A |
| CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN |
| EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, |
| FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| PERMIT FEE ATTRIBUTED TO PLANS REVIEW. THE ADDITIONAL |
| FEE FOR THIS PLAN WILL BE $950.00 . FS 553.80(2)(B) |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |