Plan Review Notes
Plan Review Notes For Permit 18051263
Permit Number 18051263
Review Stop P
Sequence Number 2
Notes
Date Text
2018-09-07 12:55:28REVIEW COMPLETED BY JERALD SMITH 0017-P
2018-09-06 12:30:352ND REVIEW: FBC 2017 6TH EDITION
 PERMIT 18051263
 PLUMBING COMMENTS:
 1ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. P.2 ARE ALL THESE DETAILS BEING USED. REMOVE
 THE ONES THAT DON'T APPLY TO THIS PROJECT. PER WPB
 AMEND TO FBC 107.2.1
  A. DETAIL A, AS PREVIOUSLY NOTED PLEASE SHOW FLOOR
 DRAIN ON SANITARY ISOMETRIC AND FLOOR PLAN; IF NOT
 REQUIRED THEN PLEASE REMOVE DETAIL.
  B. DETAIL H, IF WATER HEATER IS EXISTING, PLEASE
 REMOVE DETAIL. IF NEW WATER HEATER IS REQUIRED THEN A
 VACUUM BREAKER IS REQUIRED ON A BOTTOM FEED HEATER
 (SHOWN). PER FBC RES P2804.7
 2. SHT. P.1 AND SHEET P.3, FBC RES P3005.4.1 ALLOWS
 MAXIMUM 6 DFU ON 2" HORIZONTAL FIXTURE BRANCH. DFU LOAD
 ON THE FIXTURE BRANCH SHOWN ON ISOMETRIC AND FLOOR PLAN
 CONNECTING KITCHEN SINK/DISHWASHER AND THE WASHING
 MACHINE FIXTURE DRAINS IS 7 DFU. SIZE OF FIXTURE BRANCH
 MUST BE INCREASED TO ACCOMMODATE THE DFUS ON THE
 BRANCH.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711