2018-06-25 16:25:561ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. P.2 ARE ALL THESE DETAILS BEING USED. REMOVE
 THE ONES THAT DON'T APPLY TO THIS PROJECT. PER WPB
 AMEND TO FBC 107.2.1
 2. SHT. P.2 IS THE WATER HEATER BEING REPLACED IF SO A
 VACUUM BREAKER IS REQUIRED ON A BOTTOM FEED HEATER. PER
 FBC RES P2804.7
 3. SHT. P-2 DETAIL A SHOW FLOOR DRAIN ON SANITARY
 ISOMETRIC. PER WPB AMEND TO FBC 107.2.1
 4. SHT P-2 WHAT IS THE DRY WELL SERVING IS IT THE AC
 CONDENSATE. PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  