Plan Review Notes For Permit 18051263 |
Permit Number |
18051263 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-06-25 16:25:56 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | PLUMBING COMMENTS: | | | | 1. SHT. P.2 ARE ALL THESE DETAILS BEING USED. REMOVE | | THE ONES THAT DON'T APPLY TO THIS PROJECT. PER WPB | | AMEND TO FBC 107.2.1 | | 2. SHT. P.2 IS THE WATER HEATER BEING REPLACED IF SO A | | VACUUM BREAKER IS REQUIRED ON A BOTTOM FEED HEATER. PER | | FBC RES P2804.7 | | 3. SHT. P-2 DETAIL A SHOW FLOOR DRAIN ON SANITARY | | ISOMETRIC. PER WPB AMEND TO FBC 107.2.1 | | 4. SHT P-2 WHAT IS THE DRY WELL SERVING IS IT THE AC | | CONDENSATE. PER WPB AMEND TO FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|