2018-06-29 17:36:29 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 18051263 |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC R = FBC RESIDENTIAL |
| |
| 1. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS |
| REQUIRED. THE PLANS ARE TO BE STAMPED AND THE RECEIPT |
| SHOWING THAT FEES DUE, IF APPLICABLE, PROVIDED. |
| |
| AFTER ALL OTHER REVIEWS HAVE PASSED, CHECK OUT ONE SET |
| OF PLANS TO TAKE TO THE COUNTY. |
| |
| 561-233-5025 FOR MORE INFORMATION |
| |
| 2. NOTICE OF ACCEPTANCE(N.O.A.) |
| N.O.A. 14-0610.05 IS EXPIRED. PLEASE PROVIDE TWO COPIES |
| OF UPDATED N.O.A. |
| |
| 3. SHEET A-5 REFERENCES N.O.A. NO. 17-1018.05 FOR |
| WINDOWS. PROVIDE N.O.A. FOR WINDOWS AND MULL BAR. |
| HAVE THE DESIGNER OF RECORD MARK THE SELECTED WINDOWS, |
| ATTACHMENT TYPE AND STAMP AS REVIEWED. |
| |
| 4. SUPPLY ROOFING PRODUCT APPROVAL, OR INDICATE ON YOUR |
| COMMENT RESPONSE SHEET THAT THEY WILL BE A SUBMITTAL AT |
| A LATER DATE. |
| |
| 5. [FBC R401.2] DETERMINE UPLIFT THAT THE FOOTER WILL |
| RESIST FOR LIGHT FRAME CONSTRUCTION USING TABLE R401.1. |
| PROVIDE TYPE OF CONNECTOR AT BASE PLATE FOR THE |
| DETERMINED UPLIFT, OR SHOW ON CONNECTOR SCHEDULE HOW |
| THE SST-MST16 MEETS NAILING REQUIRMENTS. |
| |
| 6. [FBC R403.1.4]FOOTER TO HAVE MINIMUM 12" DEPTH BELOW |
| GRADE AND 4" ABOVE GRADE. |
| |
| 7. [FBC R401.3]PROVIDE DRAINAGE FROM FOUNDATION AS |
| OUTLINED IN R401.3 |
| |
| 8. [FBC R703.4]PROVIDE TYPE OF WINDOW/DOOR FLASHING TO |
| BE USED TO MEET REQUIREMNETS OF R703.4 |
| |
| NOTE: |
| ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| PLEASE PROVIDE TWO IDENTICAL COPIES OF ALL ITEMS |
| SUBMITTED AND A COMMENT RESPONSE SHEET. |
| |
| |
| |
| |