Plan Review Notes
Plan Review Notes For Permit 18051263
Permit Number 18051263
Review Stop B
Sequence Number 1
Notes
Date Text
2018-06-29 17:36:29****CORRECTIONS****
 W.P.B. PERMIT: 18051263
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC R = FBC RESIDENTIAL
  
 1. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS
 REQUIRED. THE PLANS ARE TO BE STAMPED AND THE RECEIPT
 SHOWING THAT FEES DUE, IF APPLICABLE, PROVIDED.
  
 AFTER ALL OTHER REVIEWS HAVE PASSED, CHECK OUT ONE SET
 OF PLANS TO TAKE TO THE COUNTY.
  
 561-233-5025 FOR MORE INFORMATION
  
 2. NOTICE OF ACCEPTANCE(N.O.A.)
 N.O.A. 14-0610.05 IS EXPIRED. PLEASE PROVIDE TWO COPIES
 OF UPDATED N.O.A.
  
 3. SHEET A-5 REFERENCES N.O.A. NO. 17-1018.05 FOR
 WINDOWS. PROVIDE N.O.A. FOR WINDOWS AND MULL BAR.
 HAVE THE DESIGNER OF RECORD MARK THE SELECTED WINDOWS,
 ATTACHMENT TYPE AND STAMP AS REVIEWED.
  
 4. SUPPLY ROOFING PRODUCT APPROVAL, OR INDICATE ON YOUR
 COMMENT RESPONSE SHEET THAT THEY WILL BE A SUBMITTAL AT
 A LATER DATE.
  
 5. [FBC R401.2] DETERMINE UPLIFT THAT THE FOOTER WILL
 RESIST FOR LIGHT FRAME CONSTRUCTION USING TABLE R401.1.
 PROVIDE TYPE OF CONNECTOR AT BASE PLATE FOR THE
 DETERMINED UPLIFT, OR SHOW ON CONNECTOR SCHEDULE HOW
 THE SST-MST16 MEETS NAILING REQUIRMENTS.
  
 6. [FBC R403.1.4]FOOTER TO HAVE MINIMUM 12" DEPTH BELOW
 GRADE AND 4" ABOVE GRADE.
  
 7. [FBC R401.3]PROVIDE DRAINAGE FROM FOUNDATION AS
 OUTLINED IN R401.3
  
 8. [FBC R703.4]PROVIDE TYPE OF WINDOW/DOOR FLASHING TO
 BE USED TO MEET REQUIREMNETS OF R703.4
  
 NOTE:
 ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 PLEASE PROVIDE TWO IDENTICAL COPIES OF ALL ITEMS
 SUBMITTED AND A COMMENT RESPONSE SHEET.
  
  
  
  