2018-06-01 12:19:15PERMIT # 18051261
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) PER CHAPTER 18 (NFPA 1): FIRE DEPARTMENT ACCESS
 SHALL HAVE AN UNOBSTRUCTED WIDTH OF NOT LESS THAN 20
 FEET AND AN UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS
 THAN 13 FEET 6 INCHES.
  
 2) IF ACCESS GATES WILL BE SECURED BY A LOCK AND/OR
 CHAIN, IT IS RECOMMENDED THAT A KNOX KEY PADLOCK BY
 PROVIDED FOR EMERGENCY ACCESS.
  
 3) FENCING SHALL NOT BE PLACED IN A MANNER THAT
 OBSTRUCTS ACCESS TO ANY FIRE HYDRANTS AND/OR FIRE
 DEPARTMENT CONNECTIONS.
  
  