Plan Review Notes
Plan Review Notes For Permit 18051261
Permit Number 18051261
Review Stop B
Sequence Number 1
Notes
Date Text
2018-06-09 08:53:56****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. REVISE PLAN OR APPLICATION TO INDICATE REASON FOR A
 TEMPORARY FENCE, FBC 107.
  
 2. IF THIS IS ASSOCIATED WITH A CONSTRUCTION PROJECT,
 REVISE PLAN TO SHOW COMPLIANCE WITH FBC B 3306.1,
 PROTECTION OF PEDESTRIANS. PROVIDE A SITE PLAN TO SHOW
 LOCATION OF PROPOSED CONSTRUCTION, HEIGHT OF PROPOSED
 CONSTRUCTION, AND DISTANCE TO PROPERTY LINES. IF A
 BARRIER OR BARRIER AND COVERED WALKWAY ARE REQUIRED,
 INDICATE SUCH ON THE PLAN.
  
 NOT ENOUGH INFORMATION WAS PROVIDED TO DETERMINE CODE
 COMPLIANCE.
  