2018-07-08 07:34:48 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. (ELECTRICAL NOTES M-10, M-11) ON SUBMITTED PLAN ARE |
| BEYOND THE SCOPE OF WORK FOR AN ES LICENSE HOLDER. |
| ELECTRICAL SUB-PERMIT (18051250) CANNOT BE ISSUED. AN |
| ER OR EC LICENSE HOLDER (LICENSED ELECTRICIAN) MUST |
| PERFORM WORK NEEDED TO MEET DISCONNECT REQUIREMENTS OF |
| NEC 600.6A(1) |
| |
| PLEASE SEE SCOPE OF WORK FOR ES LICENSE: |
| |
| F.S. 489.505 (#19) AND F.A.C. 61G6-7.001 SIGN |
| CONTRACTORS SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN |
| SPECIALTY CONTRACTOR) THE SCOPE OF CERTIFICATION |
| INCLUDES THE STRUCTURAL FABRICATION INCLUDING CONCRETE |
| FOUNDATION, ERECTION, INSTALLATION, ALTERATION, REPAIR, |
| SERVICE AND WIRING OF ELECTRICAL SIGNS AND OUTLINE |
| LIGHTING. THE SCOPE OF CERTIFICATION SHALL NOT INCLUDE |
| THE PROVISION OF, OR ANY ELECTRICAL WORK BEYOND, THE |
| LAST DISCONNECT MEAN OR TERMINAL POINTS. HOWEVER, A |
| CONTRACTOR CERTIFIED UNDER THIS SECTION MAY PROVIDE THE |
| ELECTRICAL ENTRANCE REQUIREMENTS FOR METERING AND MAIN |
| DISCONNECT OF REMOTE BILLBOARDS OR SIGNS WHICH ARE |
| INDEPENDENT OF ANY STRUCTURE OR BUILDING AND WHICH |
| REQUIRE NO MORE THAN TWENTY-FIVE (25) KILOWATTS AT TWO |
| HUNDRED FIFTY (250) VOLTS MAXIMUM. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| FRANK GIAQUINTO |
| ELECTRICAL INSPECTOR |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WPB |
| [email protected] |
| CELL: 561-657-1653 |
| |