2018-05-29 15:36:40 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| |
| 1) THERE ARE TWO ELECTRONIC DOOR STRIKES LOCATED IN TWO |
| SEPARATE STAIRWELLS. |
| |
| THESE STAIRWELLS ARE RATED AND NO EQUIPMENT IS TO BE |
| LOCATED IN THESE STAIRWELLS UNLESS IT IS RELATED TO |
| FUNCTION OF THE STAIRWELL. |
| |
| PER NFPA 101, CHAPTER 7, MEANS OF EGRESS. |
| |
| 7.2.2.5 ENCLOSURE AND PROTECTION OF STAIRS. |
| 7.2.2.5.1 ENCLOSURES. |
| 7.2.2.5.1.1 ALL INSIDE STAIRS SERVING AS AN EXIT OR |
| EXIT COMPONENT |
| SHALL BE ENCLOSED IN ACCORDANCE WITH 7.1.3.2. |
| |
| 7.1.3.2 EXITS. |
| |
| (10) PENETRATIONS INTO, AND OPENINGS THROUGH, AN EXIT |
| ENCLOSURE |
| ASSEMBLY SHALL BE LIMITED TO THE FOLLOWING: |
| (A) DOOR ASSEMBLIES PERMITTED BY 7.1.3.2.1(9) |
| (B) *ELECTRICAL CONDUIT SERVING THE EXIT ENCLOSURE |
| (C) REQUIRED EXIT DOOR OPENINGS |
| (D) DUCTWORK AND EQUIPMENT NECESSARY FOR INDEPENDENT |
| STAIR PRESSURIZATION |
| (E) WATER OR STEAM PIPING NECESSARY FOR THE HEATING OR |
| COOLING OF THE EXIT ENCLOSURE |
| (F) SPRINKLER PIPING |
| (G) STANDPIPES |
| (H) EXISTING PENETRATIONS PROTECTED IN ACCORDANCE WITH |
| 8.3.5 |
| (I) PENETRATIONS FOR FIRE ALARM CIRCUITS, WHERE THE |
| CIRCUITS |
| ARE INSTALLED IN METAL CONDUIT AND THE PENETRATIONS ARE |
| PROTECTED IN ACCORDANCE WITH 8.3.5 |
| |
| |
| THERE IS NO INDICATIONS IN THE CODE FOR THIS EQUIPMENT. |
| |
| |
| PLEASE REVIEW AND JUSTIFY WITH SPECIFIC CODE REFERENCES |
| AND NARRATIVE. |
| |
| |
| |
| 2) ADDITIONALLY TO #1 ABOVE, THERE ARE NO INDICATIONS |
| OF EXIT RE-ENTRY ON THIS FLOOR OR ANY OTHER FLOOR WHERE |
| THIS MAY BE ALLOWED. |
| |
| PER NFPA 1 & 101 |
| |
| 14.5.2.8* EVERY DOOR ASSEMBLY IN A STAIR ENCLOSURE |
| SERVING MORE THAN |
| FOUR STORIES, UNLESS PERMITTED BY 14.5.2.8.2, SHALL |
| MEET ONE OF THE |
| FOLLOWING CONDITIONS: |
| (1) RE-ENTRY FROM THE STAIR ENCLOSURE TO THE INTERIOR |
| OF THE BUILDING |
| SHALL BE PROVIDED. |
| (2) AN AUTOMATIC RELEASE THAT IS ACTUATED WITH THE |
| INITIATION OF THE |
| BUILDING FIRE ALARM SYSTEM SHALL BE PROVIDED TO UNLOCK |
| ALL STAIR |
| ENCLOSURE DOOR ASSEMBLIES TO ALLOW RE-ENTRY. |
| (3) SELECTED RE-ENTRY SHALL BE PROVIDED IN ACCORDANCE |
| WITH |
| 14.5.2.8.1. |
| [101:7.2.1.5.8] |
| |
| PLEASE REVIEW AND JUSTIFY WITH SPECIFIC CODE REFERENCES |
| AND NARRATIVE. |
| |
| |
| 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |