Plan Review Notes
Plan Review Notes For Permit 18051217
Permit Number 18051217
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-05-29 15:36:40THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE ARE TWO ELECTRONIC DOOR STRIKES LOCATED IN TWO
 SEPARATE STAIRWELLS.
  
 THESE STAIRWELLS ARE RATED AND NO EQUIPMENT IS TO BE
 LOCATED IN THESE STAIRWELLS UNLESS IT IS RELATED TO
 FUNCTION OF THE STAIRWELL.
  
 PER NFPA 101, CHAPTER 7, MEANS OF EGRESS.
  
 7.2.2.5 ENCLOSURE AND PROTECTION OF STAIRS.
 7.2.2.5.1 ENCLOSURES.
 7.2.2.5.1.1 ALL INSIDE STAIRS SERVING AS AN EXIT OR
 EXIT COMPONENT
 SHALL BE ENCLOSED IN ACCORDANCE WITH 7.1.3.2.
  
 7.1.3.2 EXITS.
  
 (10) PENETRATIONS INTO, AND OPENINGS THROUGH, AN EXIT
 ENCLOSURE
 ASSEMBLY SHALL BE LIMITED TO THE FOLLOWING:
 (A) DOOR ASSEMBLIES PERMITTED BY 7.1.3.2.1(9)
 (B) *ELECTRICAL CONDUIT SERVING THE EXIT ENCLOSURE
 (C) REQUIRED EXIT DOOR OPENINGS
 (D) DUCTWORK AND EQUIPMENT NECESSARY FOR INDEPENDENT
 STAIR PRESSURIZATION
 (E) WATER OR STEAM PIPING NECESSARY FOR THE HEATING OR
 COOLING OF THE EXIT ENCLOSURE
 (F) SPRINKLER PIPING
 (G) STANDPIPES
 (H) EXISTING PENETRATIONS PROTECTED IN ACCORDANCE WITH
 8.3.5
 (I) PENETRATIONS FOR FIRE ALARM CIRCUITS, WHERE THE
 CIRCUITS
 ARE INSTALLED IN METAL CONDUIT AND THE PENETRATIONS ARE
 PROTECTED IN ACCORDANCE WITH 8.3.5
  
  
 THERE IS NO INDICATIONS IN THE CODE FOR THIS EQUIPMENT.
  
  
 PLEASE REVIEW AND JUSTIFY WITH SPECIFIC CODE REFERENCES
 AND NARRATIVE.
  
  
  
 2) ADDITIONALLY TO #1 ABOVE, THERE ARE NO INDICATIONS
 OF EXIT RE-ENTRY ON THIS FLOOR OR ANY OTHER FLOOR WHERE
 THIS MAY BE ALLOWED.
  
 PER NFPA 1 & 101
  
 14.5.2.8* EVERY DOOR ASSEMBLY IN A STAIR ENCLOSURE
 SERVING MORE THAN
 FOUR STORIES, UNLESS PERMITTED BY 14.5.2.8.2, SHALL
 MEET ONE OF THE
 FOLLOWING CONDITIONS:
 (1) RE-ENTRY FROM THE STAIR ENCLOSURE TO THE INTERIOR
 OF THE BUILDING
 SHALL BE PROVIDED.
 (2) AN AUTOMATIC RELEASE THAT IS ACTUATED WITH THE
 INITIATION OF THE
 BUILDING FIRE ALARM SYSTEM SHALL BE PROVIDED TO UNLOCK
 ALL STAIR
 ENCLOSURE DOOR ASSEMBLIES TO ALLOW RE-ENTRY.
 (3) SELECTED RE-ENTRY SHALL BE PROVIDED IN ACCORDANCE
 WITH
 14.5.2.8.1.
 [101:7.2.1.5.8]
  
 PLEASE REVIEW AND JUSTIFY WITH SPECIFIC CODE REFERENCES
 AND NARRATIVE.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL