Plan Review Notes For Permit 18051191 |
Permit Number |
18051191 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-09-13 14:33:34 | 2ND REVIEW: FBC 2017 6TH EDITION | | PERMIT 18051191 | | PLUMBING COMMENTS: DENIED | | | | 1. A DRINKING FOUNTAIN IS REQUIRED. PER FBC PLUMBING | | 403.1 AND SHALL COMPLY WITH FBC ACC 602, 211.2 | | A. THE ARCHITECT'S RESPONSE TO THE INITIAL REQUIREMENT | | ALONG WITH THE LETTER STATING THE OCCUPANCY WOULD BE | | LESS THAN 15 DOES NOT CHANGE THE FACT THAT THE NUMBER | | OF OCCUPANTS (DEEMED 22) SHALL BE DETERMINED BY THE | | FLORIDA BUILDING CODE, BUILDING PER FBC PLUMBING 403.1 | | B. THE ONLY EXCEPTION FOR APPROVAL FOR A REDUCED | | OCCUPANCY LOAD IS NOTED IN FBC BUILDING 1004.1.2 AND | | NEEDS TO BE ADDRESSED TO THE BUILDING OFFICIAL FOR | | APPROVAL. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | JERALD SMITH | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6715 |
|