2018-06-13 09:58:30 | 1ST REVIEW: FBC 2017 6TH EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.1 SIDE |
| WALL. |
| THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM, |
| LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL AND |
| EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL. |
| |
| 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.2 REAR |
| WALL. |
| THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM |
| AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12 |
| INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE |
| OTHER SIDE. |
| |
| 3. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.7 |
| DISPENSERS. |
| TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 |
| INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS. |
| |
| 4. THE SERVICE SINK CANNOT DISCHARGE THRU THE WET VENT |
| OF THE BATHROOM GROUP, THE FIXTURE BRANCH FOR THE |
| SERVICE SICK SHALL CONNECT DOWN STREAM OF THE BATHROOM |
| GROUP. PER FBC PL 912.1 |
| |
| 5. THE LAVATORY IN THE BATHROOM SHALL ONLY HAVE |
| TEMPERED WATER DELIVERED THRU A TEMPERATURE LIMITING |
| DEVISE COMPILING WITH ASSE 1070 OR CSA B125.3 AND NSF |
| 372. PER FBC 416.5 AND 605.2.1 |
| |
| 6. A DRINKING FOUNTAIN IS REQUIRED. PER FBC PL 403.1 |
| AND SHALL COMPLY WITH FBC ACC 602, 211.2 |
| |
| 7. SHT. P-3 PROVIDE FIRE STOPPING DETAIL FOR PVC PIPE |
| AND COPPER THRU GYPSUM WALL BOARD ASSEMBLY'S. PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |