2018-05-31 17:36:061ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18051191
 5/31/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-2: THE ARCHITECTURAL PLANS SHOW THREE
 DRESSING ROOMS WHICH ARE REQUIRED TO HAVE EXHAUST
 VENTILATION AT A RATE OF 0.25 CFMS PER SF- TABLE
 403.3.1.1 FBC M.
  
 2) M-2, KEYED NOTE #4: THE CONDENSATE FROM THE AIR
 HANDLER CANNOT DRAIN INTO THE SANITARY SYSTEM PER
 SECTION 90-126 WEST PALM BEACH CODE OF ORDINANCES.
 PLEASE PROVIODE AN APPROVED PLACE OF DISPOSAL, AND SHOW
 THE PIPING RUN AND DISCHARGE LOCATION IN ACCORDANCE
 WITH SECTION 307.2.1 FBC M.
  
 3) M-2: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE NEW CONDENSER TO THE EXISTING
 STAND, AND SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE
 NOA FOR THE ANCHORING CLIP.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  