2018-05-31 17:36:06 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #18051191 |
| 5/31/18 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M-2: THE ARCHITECTURAL PLANS SHOW THREE |
| DRESSING ROOMS WHICH ARE REQUIRED TO HAVE EXHAUST |
| VENTILATION AT A RATE OF 0.25 CFMS PER SF- TABLE |
| 403.3.1.1 FBC M. |
| |
| 2) M-2, KEYED NOTE #4: THE CONDENSATE FROM THE AIR |
| HANDLER CANNOT DRAIN INTO THE SANITARY SYSTEM PER |
| SECTION 90-126 WEST PALM BEACH CODE OF ORDINANCES. |
| PLEASE PROVIODE AN APPROVED PLACE OF DISPOSAL, AND SHOW |
| THE PIPING RUN AND DISCHARGE LOCATION IN ACCORDANCE |
| WITH SECTION 307.2.1 FBC M. |
| |
| 3) M-2: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR |
| INSTALLATION OF THE NEW CONDENSER TO THE EXISTING |
| STAND, AND SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE |
| NOA FOR THE ANCHORING CLIP. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| |