2018-06-07 16:10:47 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE SHOW WINDOW OUTLETS AND CIRCUIT PER NEC |
| 210.62 |
| 2. PROVIDE EXTERIOR LIGHTING CONTROLS AS SPECIFIED IN |
| THE FBC ENERGY CONSERVATION FOR SIGN AND SHOW WINDOW |
| OUTLETS. FBC EC C405.2.5 |
| 3. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES |
| EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN |
| RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2 |
| 4. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS |
| STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT |
| SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2 |
| 5. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C |
| EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER CODE. NEC |
| 210.63 |
| 6. WATER HEATER LOAD DOES NOT MATCH THE SPECIFIED |
| TANKLESS HEATER ON SHEET P-1. PROVIDE CORRECTION. NEC |
| 220; WPB FBC 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |