Plan Review Notes
Plan Review Notes For Permit 18051191
Permit Number 18051191
Review Stop E
Sequence Number 1
Notes
Date Text
2018-06-07 16:10:47CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE SHOW WINDOW OUTLETS AND CIRCUIT PER NEC
 210.62
 2. PROVIDE EXTERIOR LIGHTING CONTROLS AS SPECIFIED IN
 THE FBC ENERGY CONSERVATION FOR SIGN AND SHOW WINDOW
 OUTLETS. FBC EC C405.2.5
 3. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 4. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2
 5. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER CODE. NEC
 210.63
 6. WATER HEATER LOAD DOES NOT MATCH THE SPECIFIED
 TANKLESS HEATER ON SHEET P-1. PROVIDE CORRECTION. NEC
 220; WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  