Plan Review Notes
Plan Review Notes For Permit 18051063
Permit Number 18051063
Review Stop B
Sequence Number 2
Notes
Date Text
2018-05-23 08:48:58PASSED WITH PROVISO; NOTIFIED APPLICANT VIA EMAIL
  
 THE MULLION IS SCANNED IN REVERSE ORDER. I'VE
 RE-SCANNED IT AND ATTACHED IT - THE NEW DOCUMENT HAS
 THE SAME NAME BUT INCLUDES THE FL NUMBER AT THE END.
  
 THE WIND PRESSURE DIAGRAM DOESN'T INDICATE MEAN ROOF
 HEIGHT. YOU CAN WRITE THIS ON YOUR WIND PRESSURE CHART
 OR FLOOR PLAN RATHER THAN MARKING UP THE ENGINEERING.
  
 FOR $250 YOU CAN "MASTER" A WIND LOAD CHART FOR EACH
 BUILDING; THEN YOU DON'T NEED TO PROVIDE AN ORIGINAL
 FOR EACH JOB.
  
 THE DESIGN PRESSURES DON'T MATCH THE ENGINEERING, SEE
 BELOW. OPENINGS 1 AND 2 ARE OK, 3 SHOULD BE
 -65.9/+65.9, 4 SHOULD BE -64.5/+63.6. SINCE SMALLER
 OPENINGS HAVE HIGHER DESIGN PRESSURES, YOU NEED TO USE
 THE SMALLER COLUMN.