2018-08-28 07:50:08 | 2ND REVIEW: |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. THE VENT MAYBE REQUIRED TO BE LARGER THAN 2IN. . |
| VENTS EXCEEDING 40 FEET IN DEVELOPED LENGTH SHALL BE |
| INCREASED BY ONE NOMINAL PIPE SIZE FOR THE ENTIRE |
| DEVELOPED LENGTH OF THE VENT PIPE. INDICATE LENGTH OF |
| ALL CONNECT VENTS ON PLAN. PER FBC PL 906.2 |
| |
| 2. THE DRINKING FOUNTAIN IS MISSING FROM THE WATER |
| ISOMETRIC PLEASE CLARIFY.WPB AMEND TO FBC 107.2.1 |
| |
| 3. PREVIOUS COMMENT: ON THE SANITARY ISOMETRIC THE |
| SHOWER IN THE STAFFF BATHROOM IS STILL LABELED AS A |
| FLOOR DRAIN WITH A TRAP PRIMER PLEASE LABEL ALL FIXTURE |
| TO MATCH THE FIXTURES THEY SERVE. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| 4. ON THE SANITARY ISOMETRIC PLEASE CORRECT THE |
| FOLLOWING THE LAVATORY IN THE STAF BATHROOM IS NOT |
| MARKED, THE BREAKROOM SINK AND THE MOP SINK ARE MARKED |
| AS A LAVATORY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 5. ON THE SANITARY ISOMETRIC IN THE STAFF BATHROOM WITH |
| THE SHOWER THE LAVATORY BRANCH DRAIN SHALL CONNECT |
| BETWEEN THE TOILET AND SHOWER, TWO FIXTURE ARE NPT |
| PERMITTED UP STREAM OF THE VENT ON A WET VENT SYSTEM. |
| PER FBC PL 912.1 |
| |
| 6. THE DRINKING FOUNTAIN IS MISSING THE VENT ON THE |
| ISOMETRIC DRAWING. PLEASE CLARIFY. PER FBC PL 901.2.1 |
| |
| 7. ON SHT. A9.0.2 IT APPEARS THAT THE INSIDE CLEAR |
| DIMENSION OF THE TRANSFER SHOWER IN THE STAFF BATHROOM |
| IS SHOWING 3'-11/4" IT SHALL BE 36" INSIDE DIMENSION. |
| FBC ACC 608.2.1 |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561-805-6711 |
| [email protected] |
| |