Plan Review Notes
Plan Review Notes For Permit 18051051
Permit Number 18051051
Review Stop P
Sequence Number 2
Notes
Date Text
2018-08-28 07:50:082ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE VENT MAYBE REQUIRED TO BE LARGER THAN 2IN. .
 VENTS EXCEEDING 40 FEET IN DEVELOPED LENGTH SHALL BE
 INCREASED BY ONE NOMINAL PIPE SIZE FOR THE ENTIRE
 DEVELOPED LENGTH OF THE VENT PIPE. INDICATE LENGTH OF
 ALL CONNECT VENTS ON PLAN. PER FBC PL 906.2
  
 2. THE DRINKING FOUNTAIN IS MISSING FROM THE WATER
 ISOMETRIC PLEASE CLARIFY.WPB AMEND TO FBC 107.2.1
  
 3. PREVIOUS COMMENT: ON THE SANITARY ISOMETRIC THE
 SHOWER IN THE STAFFF BATHROOM IS STILL LABELED AS A
 FLOOR DRAIN WITH A TRAP PRIMER PLEASE LABEL ALL FIXTURE
 TO MATCH THE FIXTURES THEY SERVE. PER WPB AMEND TO FBC
 107.2.1
  
 4. ON THE SANITARY ISOMETRIC PLEASE CORRECT THE
 FOLLOWING THE LAVATORY IN THE STAF BATHROOM IS NOT
 MARKED, THE BREAKROOM SINK AND THE MOP SINK ARE MARKED
 AS A LAVATORY. PER WPB AMEND TO FBC 107.2.1
  
 5. ON THE SANITARY ISOMETRIC IN THE STAFF BATHROOM WITH
 THE SHOWER THE LAVATORY BRANCH DRAIN SHALL CONNECT
 BETWEEN THE TOILET AND SHOWER, TWO FIXTURE ARE NPT
 PERMITTED UP STREAM OF THE VENT ON A WET VENT SYSTEM.
 PER FBC PL 912.1
  
 6. THE DRINKING FOUNTAIN IS MISSING THE VENT ON THE
 ISOMETRIC DRAWING. PLEASE CLARIFY. PER FBC PL 901.2.1
  
 7. ON SHT. A9.0.2 IT APPEARS THAT THE INSIDE CLEAR
 DIMENSION OF THE TRANSFER SHOWER IN THE STAFF BATHROOM
 IS SHOWING 3'-11/4" IT SHALL BE 36" INSIDE DIMENSION.
 FBC ACC 608.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
2018-08-27 09:49:53REVIEW BY GEORGE JOHNSON.