Plan Review Notes
Plan Review Notes For Permit 18051051
Permit Number 18051051
Review Stop P
Sequence Number 1
Notes
Date Text
2018-07-05 14:51:431) INDICATE THE LEVEL OF ALTERATION ON BOTH SETS OF
 PLANS PER THE 2017 FBC-EXISTING SECTION 301.1.
 2) SHT. L-3 - SHOW THE LOCATION OF THE IRRIGATION PUMP,
 CONTROLLER AND RAIN SENSOR. ALSO, SHOW THE WATER SOURCE
 FOR THE IRRIGATION SYSTEM ON THE PLAN. IF CONNECTED TO
 CITY WATER, A REDUCED PRESSURE ZONE BACKFLOW PREVENTION
 DEVICE WILL BE REQUIRED ON THE IRRIGATION SYSTEM.CWPB
 CROSS-CONNECTION CONTROL MANUAL & WPB AMEND. TO FBC
 SEC. 107.2.1.
 3) PLACE A NOTE ON SHT. L-3 THAT IRRIGATION HEADS SHALL
 BE PLACED A MINIMUM OF ONE FOOT AWAY FROM THE STRUCTURE
 SIDEWALL. 2017 FBC- PLUMBING SEC.318.1.
 4) SHT. ALS 1.1 - PLUMBING FIXTURE REQUIREMENTS - THE
 TOILET FACILITIES ARE NOTED AS "UNISEX." THE TOILET
 ROOMS MUST BE DESIGNATED AS "MALE" AND "FEMALE" IN
 ACCORDANCE WITH THE 2017 FBC-PLUMBING SEC. 403.2.
 5) SHT. A9.0.2 - SHOW THE CLEAR INSIDE DIMENSIONS ( L X
 W ) OF THE ALL THE TOILET ROOMS ON THE PLANS. WPB
 AMEND. TO FBC SEC. 107.2.1.
 6) SHT. A9.0.2. - SHOW THE INSIDE CLEAR DIMENSIONS OF
 THE ACCESSIBLE SHOWER IN THE STAFF TOILET ROOM ON THE
 PLANS. COMPLY WITH 2017 FBC-ACCESS. SEC.608.2.
 7) SHOW THE DIMENSIONS OF THE CLEAR FLOOR SPACES FOR
 THE HANDICAPPED ACCESSIBLE FIXTURES. COMPLY WITH 2017
 FBC-ACCESS. SECS. 608.2.1, 604.3, 606.2
 8) SHT. A9.0.1 - THE STAFF ROOM SINK SHALL COMPLY WITH
 2017 FBC-ACCESSIBILITY SEC.606.2.
 9) SUBMIT A RAINWATER RISER AND SHOW THE SIZE OF THE
 ROOF DRAINS ON SHT. A2.0.1 AND HOW YOU ARRIVED AT THE
 ROOF DRAIN SIZE. COMPLY WITH 2017 FBC-PLUMBING
 SEC.1106.2.
 10) SHT. A5.0.2 - SUBMIT CALCULATIONS FOR THE SIZING OF
 THE INTEGRAL GUTTERS AT THE ROOF EDGE. COMPLY WITH
 TABLE 1106.6 OF THE 2017 FBC-PLUMBING.
 11) SHT. A9.0.1 -THE REFRESHMENT CENTER CABINET HEIGHT
 SHALL BE A MAXIMUM OF 34 INCHES IN HEIGHT. 2017
 FBC-ACCESS. SEC.902.3. IDENTIFY THE REFRESHMENT CENTER
 ON SHT. A9.0.2.
 12) SHT.A9.0.1 - TTHE MAXIMUM HEIGHT OF THE SINK
 CABINET IN THE STAFF LOUNGE SHALL BE 34 INCHES MAXIMUM
 PER 2017 FBC-ACCESS. SEC.902.3.
 13) SHT. A9.0.2 - DETAILS A, B & C - DETAIL A NOTES THE
 TOILET ROOMS AS #104 & #105 BUT THE FLOOR PLAN SHOWS
 #118 & 119.THE SAME TYPE OF DISCREPANCY OCCURS ON
 DETAILS B & C. CLARIFY.
 14) TOILET ROOM #111 - THE DOOR CANNOT SWING INTO THE
 CLEAR FLOOR SPACE FOR THE LAVATORY PER THE 2017
 FBC-ACCESS. SEC.603.2.3.
 15) SHT. A9.0.2 - SHOW THE HEIGHT OF THE SHOWER SEAT.
 COMPLY WITH 2017 FBC- ACCESS. SECS. 610.3, 610.3.2.
 16) THE GRAB BARS IN THE TRANSFER SHOWER SHALL COMPLY
 WITH 2017 FBC-ACCESS. SEC.608.3.1 ANSD FIG.608.3.1.
 17) THE LOCATION OF THE SHOWER CONTROLS IN THE STAFF
 TOILET SHOWER SHALL COMLY WITH 2017 FBC-ACCESS.
 SEC.608.5.1.
 18) THE SHOWER SPRAY UNIT IN THE STAFF TOILET SHOWER
 SHALL COMPLY WITH 2017 FBC-ACCESS. SEC.608.6.
 19) SUBMIT DETAILS FOR THE REQUIRED REINFORCEMENT FOR
 FUTURE GRAB BARS IN THE PRIVATE TOILET. SHOW THE TYPE
 OF MATERIAL, LENGTH, WIDTH AND HEIGHT OF THE
 REINFORCEMENT. 2017 FBC-ACCESS. SECS.604.5, 609.8.
 22) SHT. A10.0.1 - DETAIL #11 - THE SHOWER FLOOR SHALL
 BE PITCHED A MINIMUM OF 1/4 INCH PER FOOT TO THE DRAIN.
 2017 FBC-PLUMBING SEC.417.5.2.
 23) SHT.A10.0.2. - DETAIL #7 - THE MAXIMUM HEIGHT OF
 THE CABINET AT THE STAFF LOUNGE SHALL BE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR.2017 FBC-ACCESS.
 SEC.902.3.
 24) THE REACH RANGES AT THE CABINETS SHALL COMPLY WITH
 2017 FBC-ACCESS. SEC.308.3.2,
 25) SHT. P2.1 SHOWS ALL THE VENTS THROUGH THE ROOF AND
 ALSO LOOPED TOGETHER. WHICH IS IT? CLARIFY. A MINIMUM
 OF ONE MMAIN VENT THROUGH THE ROOF IS REQUIRED. 2017
 FBC-PLUMBING SEC.904.1.
 26) SHT. P0.1 - THE SHOWERS ARE SHOWN AS FLOOR DRAINS
 WITH TRAP PRIMERS ON THE SANITARY RISERS. REVISE THE
 RISER AND CORRECTLY IDENTIFY ALLL THE FIXTURES ON THE
 SANITARY RISER.ID
 27) SHT.P0.1 - PLUMBING NOTES - THERE ARE SEVERAL NOTES
 THAT REFER TO THE 2010 FBC. CORRECT THE NOTES TO REFER
 TO THE 2017 FBC. THIS ALSO OCCURS AT THE WATER HEATER
 DETAIL.
 28) THE WATER HEATER TEMPERATURE AND RELIEFF LIINE
 SHALL DISCHARGE TO THROUGH AN AIR GAP LOCATED IN THE
 SAME ROOM AS THE WATTER HEATER. 2017 FBC-PLUMBING
 SEC.504.6 (2)
 29) TEMPERED WATER IS REQUIRED TO THE LAVATORIES IN THE
 TOILET ROOMS.2017 FBC-PLUMBING SEC.607.1. TEMPERED
 WATER SHALL BE SUPPLIED THROUGH A WATER TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070. 2017
 FBC-PLUMBING SEC.607.1.2.
 30 ) HOT WATER IS REQUIRED TO THE STAFF LOUNGE SINK AND
 THE MOP SINK. 2017 FBC-PLUMBING SEC. 607.1.
 31) THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER
 PIPING FROM THE HOT WATER SOURCE TO THE FIXTURES SHALL
 NOT EXCEED 50 FEET.2017 FBC-PLUMBING SEC.607.2.
 32) HOT WATER PIPE SHALL BE INSULATED IN ACCORDANCE
 WITH FBC-PLUMBING SEC.607.5.
 33) SHOW THE SIZE OF THE EXPANSION TANK ON THE WATER
 HEATER DETAIL.
 34) SHOW THE WIDTH OF THE PROPOSED ADAPTABLE SHOWER IN
 THE PRIVATE TOILET.
 35) A 30 INCH WIDE MINIMUM BY 48 INCH LONG MINIMUM
 CLEARANCE SHALL BE PROVIDED ADJACENT TO THE OPEN FACE
 OF THE SHOWER COMPARTMENT. THE SHOWER DOES NOT COMPLY
 DUE TO THE LOCATION OF THE WATER CLOSET. 2017 FBC
 -ACCESS. SECS. 608.2.2.1 & FIGURE 608.2.2.
 36) A CLEARANCE OF 36 INCHES WIDE MINIMUM BY 48 INCHES
 LONG MINIMUM MEAURED FROM THE CONTROL WALL SHALL BE
 PROVIDED FOR THE ACCESSIBLE SHOWER IN THE STAFF TOILET.
 2017 FBC _ ACCESS. SEC.608.2.1 & FIGURE 608.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW