2018-06-25 15:29:06 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #18051051 |
| 6/25/18 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M6.1: THE O/A CALCULATIONS FOR AHU-1 ARE |
| INCORRECT ACCORDING TO TABLE 403.3.1.1 FBC M. THE TOTAL |
| NUMBER OF PEOPLE FOR CONFERENCE ROOMS IS BASED ON 50 |
| PERSONS PER SQ. FT. PLEASE CORRECT THE CALCULATIONS AND |
| THE OUTDATED CODE REFERENCE. |
| |
| 2) M2.1: PLEASE REVISE NOTE #2 TO INDICATE THE ACCESS |
| HATCH WILL BE SIZED LARGE ENOUGH TO REMOVE AND REPLACE |
| THE AIRHANDLER, AND A LEVEL WORKING SPACE NOT LESS THAN |
| 30 INCHES DEEP AND 30 INCHES WIDE SHALL BE PROVIDED IN |
| FRONT OF THE CONTROL SIDE OF THE UNIT- SECTION 306.1 |
| FBC M. |
| |
| 3) M2.1: PLEASE PROVIDE A NOTE ON THE PLAN TO INDICATE |
| THE EXTERIOR CONDENSERS WILL BE INSTALLED TO PROVIDE |
| WORKING CLEARANCES PER THE MANUFACTURER, AND IN |
| ACCORDANCE WITH SECTION 306.1 FBC M. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |