2018-06-25 15:29:061ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18051051
 6/25/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M6.1: THE O/A CALCULATIONS FOR AHU-1 ARE
 INCORRECT ACCORDING TO TABLE 403.3.1.1 FBC M. THE TOTAL
 NUMBER OF PEOPLE FOR CONFERENCE ROOMS IS BASED ON 50
 PERSONS PER SQ. FT. PLEASE CORRECT THE CALCULATIONS AND
 THE OUTDATED CODE REFERENCE.
  
 2) M2.1: PLEASE REVISE NOTE #2 TO INDICATE THE ACCESS
 HATCH WILL BE SIZED LARGE ENOUGH TO REMOVE AND REPLACE
 THE AIRHANDLER, AND A LEVEL WORKING SPACE NOT LESS THAN
 30 INCHES DEEP AND 30 INCHES WIDE SHALL BE PROVIDED IN
 FRONT OF THE CONTROL SIDE OF THE UNIT- SECTION 306.1
 FBC M.
  
 3) M2.1: PLEASE PROVIDE A NOTE ON THE PLAN TO INDICATE
 THE EXTERIOR CONDENSERS WILL BE INSTALLED TO PROVIDE
 WORKING CLEARANCES PER THE MANUFACTURER, AND IN
 ACCORDANCE WITH SECTION 306.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
 HTTPS://WWW.SURVEYMONKEY.COM/R/WESTPALMBEACHCONSTRUCTIO
 NSERVICES
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved