Plan Review Notes
Plan Review Notes For Permit 18051008
Permit Number 18051008
Review Stop M
Sequence Number 1
Notes
Date Text
2018-06-21 16:48:231ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18051008
 6/21/18
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 RTU- SECTION C403.2.1 FBC-17 FBC EC.
  
 2) PROVIDE COMPLETE SITE SPECIFIC ENGINEERING FOR
 INSTALLATION OF THE NEW RTU PER SECTION 301.15. PLEASE
 NOTE THE DETAILS ON SHEET M6.1 ARE MARKED "FOR
 REFERENCE ONLY", AND "CODE COMPLIANCE SHALL BE
 DETERMINED AND VERIFIED BY A LICENSED STRUCTURAL
 ENGINEER".
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
 HTTPS://WWW.SURVEYMONKEY.COM/R/WESTPALMBEACHCONSTRUCTIO
 NSERVICES
  