Plan Review Notes For Permit 18051008 |
Permit Number |
18051008 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-06-21 16:48:23 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #18051008 | | 6/21/18 | | | | CODES IN EFFECT: | | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW | | RTU- SECTION C403.2.1 FBC-17 FBC EC. | | | | 2) PROVIDE COMPLETE SITE SPECIFIC ENGINEERING FOR | | INSTALLATION OF THE NEW RTU PER SECTION 301.15. PLEASE | | NOTE THE DETAILS ON SHEET M6.1 ARE MARKED "FOR | | REFERENCE ONLY", AND "CODE COMPLIANCE SHALL BE | | DETERMINED AND VERIFIED BY A LICENSED STRUCTURAL | | ENGINEER". | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | HTTPS://WWW.SURVEYMONKEY.COM/R/WESTPALMBEACHCONSTRUCTIO | | NSERVICES | | |
|