Plan Review Notes
Plan Review Notes For Permit 18051002
Permit Number 18051002
Review Stop E
Sequence Number 2
Notes
Date Text
2018-06-08 07:05:46THE PLAN HAS BEEN PASSED PROVISIONALLY: FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECT FEE(S)
  
 1. PROVIDE PANEL SCHEDULE AND LOAD CALCULATION BY FINAL
 INSPECTION. PERMIT REFERENCED BY CONTRACTOR #18040526
 IS A STAND ALONE SERVICE CHANGE PERMIT WITH NO PANEL
 SCHEDULE OR LOAD CALCULATION.
  
 2. EGRESS LIGHTING REQUIRED AT ALL ENTRANCES/EXIT DOORS
 TO THE DWELLING EXECPT THE (VEHICLE DOOR) FOR THE
 GARAGE. FOR DWELLING UNITS, ATTACHED GARAGES, AND
 DETACHED GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE
 LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B),
 FBC RE E3903.3
  
 3. VALUE HAS BEEN ADJUSTED TO 4500$ THE INCREASED VALUE
 OF 1000$ ADDED TO THE INITIAL 2000$ TO MAKE 3000$ TOTAL
 IS INSUFFICIENT.
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  