Plan Review Notes For Permit 18050972 |
Permit Number |
18050972 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-07-23 15:18:59 | 07/23/2018 1ST PLUMBING/POOL REVIEW **DENIED** WITH | | COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. THE DYNAMIC HEAD CALCULATIONS FOR THE MAXIMUM SYSTEM | | FLOW DOES NOT SHOW ALL FRICTION LOSS THROUGH ALL | | COMPONENTS, CHLORINATORS, HEATER, ETC., ON THE HAYWARD | | CALCULATOR CHART. ASSUME THE TOTAL FRICTION LOSS WOULD | | INCLUDE THE PIPE, FITTINGS (90-DEGREE FITTINGS, 45'S, | | TEES) AND ALSO VALVES AND FILTER. PLEASE CLARIFY, WPB | | AMENDMENT. TO FBC SEC. 107.2.1. INFORMATION ON | | CONSTRUCTION DOCUMENTS. | | | | LUIS A. CRESPO | | PLUMBING INSPECTOR / | | PLUMBING PLAN REVIEW | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | [email protected] | | 561-805-6720 | | |
|