Plan Review Notes
Plan Review Notes For Permit 18050972
Permit Number 18050972
Review Stop P
Sequence Number 1
Notes
Date Text
2018-06-02 05:36:431) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM
 ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC
 7 ? 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 EDITION
 ADDRESSES FLOW RATE IN GALLONS PER MINUTE (GPM). IT
 REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED
 THE LISTED MAXIMUM FLOW RATE OF THE SUCTION OUTLET
 FITTING ASSEMBLY (DRAIN COVER).
 2) SHT. 2 - VAC LINE DETAIL SHOWS THE VAC LINE AT 18
 INCHES MAIXXIMUM BELOW THE WATER LEVEL BUT THE NOT
 STATEES THAT THE VAC LINE SHALL NOT BE GREATER THAN 12
 INCHES BELOW THE MINIMUM WATER LEVEL PER ANSI /NSPI 5.
 ALSO, SEE NOTE ON SHT.1 THAT REFERS TO THE 18 INCHES
 BELOW THE WATER LEVEL PER ANSI/NSPI 5. THESE NOTES AND
 DETAIL ARE CONFLICTING. WHICH IS IT, 18 OR 12 INCHES?
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN
 DRAIN AND THE PUMP. WPB AMEND. TO FBC SEC. 107.2.1.
 4) REVISE GENERAL NOTE #8 TO REFER TO THE 2013 EDITION
 OF APSP 7.
 5) SUBMIT DOCUMENTATION THAT THE GAS POOL HEATER MEETS
 THE MINIMUM REQUIRED EFFFICIENCY AS REQUIRED BY THE
 2017 FBC-ENERGY SEC.R403.10.4.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW