Plan Review Notes For Permit 18050963 |
Permit Number |
18050963 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-06-18 06:06:19 | 06/18/2018 2ND GAS REVIEW**DENIED** | | | | 1) EXISTING POOL HEATER EVEN WITH IT BEING CAPPED OF | | MUST HAVE THE BTU'S INCLUDED AS IT COULD ONE DAY BE | | RECONNECTED INTO THE SYSTEM. LIST THE BTU LOAD OF EACH | | APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER | | TO THE 2017 FBC-FUEL GAS SECS.401.8, 402.2, AND TABLES | | 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC. | | G2413.3, G2413.4 AND TABLES G2413.4 (1 ) THROUGH | | G2413.4 (21). WOULD ACCEPT LETTER FROM OWNER ADVISING | | THAT A GAS POOL HEATER WOULD NEVER BE REINSTALLED AS | | CURRENTLY IS USING HEAT PUMP. | | | | 2) MUST INCLUDE APPLIANCES THAT ARE CONNECTED INTO THE | | SYSTEM. THE MASTER BATHROOM HAS ITS OWN GAS WATER | | HEATER THAT IS NOT SHOWN ON THE ISOMETRIC. LIST THE BTU | | LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON THE | | SYSTEM. REFER TO THE 2017 FBC-FUEL GAS SECS.401.8, | | 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) OR 2017 | | FBC-RES. SEC. G2413.3, G2413.4 AND TABLES G2413.4 (1 ) | | THROUGH G2413.4 (21). | | | | | | TIM HUNT | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | 561-805-6695 | | [email protected] |
|