Plan Review Notes
Plan Review Notes For Permit 18050963
Permit Number 18050963
Review Stop G
Sequence Number 2
Notes
Date Text
2018-06-18 06:06:1906/18/2018 2ND GAS REVIEW**DENIED**
  
 1) EXISTING POOL HEATER EVEN WITH IT BEING CAPPED OF
 MUST HAVE THE BTU'S INCLUDED AS IT COULD ONE DAY BE
 RECONNECTED INTO THE SYSTEM. LIST THE BTU LOAD OF EACH
 APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER
 TO THE 2017 FBC-FUEL GAS SECS.401.8, 402.2, AND TABLES
 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC.
 G2413.3, G2413.4 AND TABLES G2413.4 (1 ) THROUGH
 G2413.4 (21). WOULD ACCEPT LETTER FROM OWNER ADVISING
 THAT A GAS POOL HEATER WOULD NEVER BE REINSTALLED AS
 CURRENTLY IS USING HEAT PUMP.
  
 2) MUST INCLUDE APPLIANCES THAT ARE CONNECTED INTO THE
 SYSTEM. THE MASTER BATHROOM HAS ITS OWN GAS WATER
 HEATER THAT IS NOT SHOWN ON THE ISOMETRIC. LIST THE BTU
 LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON THE
 SYSTEM. REFER TO THE 2017 FBC-FUEL GAS SECS.401.8,
 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) OR 2017
 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES G2413.4 (1 )
 THROUGH G2413.4 (21).
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]